IAC

B&R 0PS1042.2

100 to 240 VAC wide-range input Can be connected in parallel for increased capacity and redundancy Reliable operation due to long power failure bypass function under full load and high MTBF (>500,000 h) International certification package Wide temperature range from -25 to 70°C Extra flat design Easy DIN rail or wall mounting 24 VDC power supply, 1-phase, 4.2 A, input 100 to 240 VAC, wide range, top-hat rail installation

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

General information
Insulation voltages / Input - Output4 kV AC (type test) 2 kV AC (routine test)
Connection cross section / Wire end sleevesFlexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950
Connection cross section / Flexible0.2 to 2.5 mm² / 24 to 12 AWG
Connection cross section / Inflexible0.2 to 2.5 mm² / 24 to 12 AWG
Certifications / CEYes
Certifications / UKCAYes
Certifications / ULcULus E123528 Industrial control equipment
Status displayGreen LED (DC OK), threshold value Uout = 21.5 V
Connection typeScrew terminal
Wire stripping length6.5 mm (input/output)
Input
Nominal input voltage100 to 240 VAC
Input voltageAC 85 to 264 V (wide range), 45 to 65 Hz DC 95 to 250 V
Input currentApprox. 1.3 A (120 VAC) Approx. 0.8 A (230 VAC)
Inrush current limiting<15 A (typical)
I²t<1 A²s
Power failure bypass>20 ms (120 VAC) >100 ms (230 VAC)
Switch-on time<0.5 s (typical)
Protective circuitTransient surge protection with varistor
Internal fuse4 A slow-blow
Required line fuse for line protection6 A (characteristic B) 10 A (characteristic B) 16 A (characteristic B)
Output
Output current / -25 to 40°C4.4 A
Output current / 40 to 55°C4.2 A
Output current / >55°CDerating: 2.5% per °C
Nominal voltage24 VDC ±1%
Output power100 W
Setting range for output voltage22.5 to 29.5 VDC (>24 VDC power constant)
Current limitingMax. 6.5 A
Control deviation<1% (static load change 10 to 90%) <2% (dynamic load change 10 to 90%) <0.1% (input voltage change ±10%)
Rise time<0.5 s (UOUT (10 to 90%))
Residual ripple<25 mVSS (at nominal values)
Switching peaks<25 mVSS (at nominal values)
Can be connected in parallelYes, to establish redundancy and increase capacity
Can be connected in seriesYes
Protection against internal overvoltagesYes, limited to approximately 35 VDC
Protective functionsOutput protected against continuous short circuit, open circuit and overload
Power back immunityMax. 35 VDC
Output noise suppressionDevice complies with EN 55011 (class B)
Efficiency, reliability
Power dissipation / Rated loadMax. 13.2 W
Power dissipation / No-load operationMax. 0.7 W
Efficiency>88% (at 230 VAC and nominal values)
MTBF>500,000 h, per IEC 61709 (SN 29500)
Operating conditions
Installation elevation above sea level / Maximum6000 m
Ventilation/CoolingNormal convection, no fan required
Degree of protection per EN 60529IP20
Protection classII
Ambient conditions
Temperature / Operation-25 to 70°C (>55°C derating)
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationMax. 95%, non-condensing
Vibration / Operation<15 Hz, amplitude ±2.5 mm, per IEC 60068-2-6 15 to 150 Hz, 2.3 g, 90 min
Shock / Operation30 g in each direction, per IEC 60068-2-27
Pollution degree2, per EN 50178
Climate category3K3, per EN 60721
Mechanical properties
Dimensions / Width90 mm
Dimensions / Height90 mm
Dimensions / Depth61 mm
InstallationEasy top-hat rail installation (DIN rail NS 35, EN 60715) or wall mounting
Weight400 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.