IAC

B&R 0PS1200.3

Minimum space requirement in the control cabinet due to a thin design Robust and reliable thanks to dynamic boost with a strong output characteristic curve for starting heavy loads Optical and preventive function monitoring with three-color LED and dry switching contact Easy handling due to push-in connections, label fields, wire stripping mark and tamper-resistant setup Can be connected in parallel for increased power and redundancy Temperature range: -25°C to +70°C Worldwide use thanks to AC and DC wide-range input International certification package 24 VDC power supply unit, 1-phase, 20 A, input 100 to 240 VAC, wide range, thin design, top-hat rail installation

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

General information
Insulation voltages / Input - Output3 kV DC (type test) 3.1 kV DC (routine test)
Insulation voltages / Input - Ground1.5 kV DC (type test) 3.1 kV DC (routine test)
Insulation voltages / Input - Signal3 kV DC (type test) 3.1 kV DC (routine test)
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)Not applicable
Certifications / ULcULus E534663 Industrial control equipment
Certifications / DNVTemperature: D (-25 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: A
Status displayGreen LED (DC OK), threshold value Uout > 21 V
Active DC OK switch outputSee section "Dry switching contact".
Connection typePush-in connection
Input
Nominal input voltage100 to 240 VAC
Input voltage100 to 240 VAC -15% to +10% 100 to 240 VDC ±10% 115 to 240 VAC ±10% (UL) 160 to 240 VDC ±10% (UL)
Network typeStar network (TN, TT, IT(PE))
Frequency50 to 60 Hz ±10%
Inrush current<21 A
Current consumption5.3 A / 2.15 A (100 VAC / 240 VAC) 4.4 A / 2.3 A (120 VAC / 230 VAC) 5.2 A / 2.1 A (100 VDC / 240 VDC)
I²t<1.091 A²s
Power failure bypassTyp. 23 ms (120 VAC) Typ. 24 ms (230 VAC)
Leakage current to PE<3.5 mA
Protective circuitVaristor transient protection
Internal fuse10 A
Required line fuse for device and line protectionSee section "Input protection".
Output
Nominal voltage24 VDC
Output power480 W / Max. 720 W (5 s)
Output voltage24 to 28 VDC
Output current20 A / Max. 30 A (5 s)
Setting range for output voltage24 to 28 VDC
Control deviation<0.1% (input voltage change ±10%) <3% (load change, dynamic) <1% (load change, static)
Rise time≤1 s (UOUT (10 to 90%))
Residual rippleTyp. 50 mVSS
Can be connected in parallelYes, for increased efficiency and redundancy
Can be connected in seriesYes, for increased output voltage (observe SELV limit)
Overvoltage protection≤35 VDC (on the output (OVP))
Protective functionsShort-circuit protection
Feedback voltage resistance≤35 VDC
Efficiency, reliability
Power dissipation / Rated load<33.37 W (120 VAC) <26.72 W (230 VAC)
Power dissipation / No-load operation<1.3 W (120 VAC) <1.37 W (230 VAC)
EfficiencyTyp. 93.49% (120 VAC) Typ. 94.42% (230 VAC)
MTBF230 VAC / >1,400,000 h (25°C) 230 VAC / >770,000 h (40°C) 230 VAC / >310,000 h (60°C)
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalNo
Installation elevation above sea level / Maximum5000 m
Flammability classV0
Ventilation/CoolingNormal convection, no fan required
Degree of protection per EN 60529IP20
Protection classI
Ambient conditions
Temperature / Operation-25 to 70°C
Temperature / DeratingSee section "Derating".
Temperature / Starting temperature-40°C
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationMax. 95%, non-condensing
Vibration / Operation10 to 50 Hz, amplitude ±0.2 mm 50 to 150 Hz, 2.3 g, 90 min, per IEC 60068-2-6
Shock / Operation18 ms, 30 g, in each direction, per IEC 60068-2-27
Pollution degree2
Climate category3K3, per EN 60721
Overvoltage categoryIII (≤2000 m) / II (≤5000 m), per EN 61010-1 III (≤2000 m) / II (≤5000 m), per EN 61010-2-201
Mechanical properties
Housing / MaterialAluminum sheet, plastic cover PA
Housing / CoatingNo protective coating
Dimensions / Width55 mm
Dimensions / Height135 mm
Dimensions / Depth132 mm
InstallationEasy top-hat rail installation (NS 35 rails, EN 60715)
Weight940 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.