B&R 0PS310.1

24 VDC power supply unit, 3-phase, 10 A, input 400..500 VAC (3 phases), wide range, top-hat rail installation

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

General information
Status indicators / Cutoff in fuse modeLED, red
Status indicators / OperationLED, green
TerminalsStable screw clamp terminal blocks
Terminal block
Connection cross section / Flexible0.5 to 4 mm² / 20 to 10 AWG
Connection cross section / Inflexible0.5 to 6 mm² / 20 to 10 AWG
Input
Input voltage2 AC and 3 AC 340 to 576 V, 47 to 63 Hz DC 450 to 820 V
Input current (at 24 V / 10 A)3 x 0.8/0.7 A at 400/500 VAC 2 x 1.2/1 A at 400/500 VAC
External fuse protectionEach phase is internally fused. External fuse protection possibly for line protection
Transient immunityTransient-proof per VDE 0160 / W2
Output (including logic)
Permissible output load / TU = 0 to 45°C24 V / 12 A or 28 V / 10.3 A (288 W)
Permissible output load / TU = 0 to 60°C24 V / 10 A or 28 V / 8.6 A (240 W)
Output noise suppressionDevice complies with EN 61000-6-3 (class B)
Output power240 W
Nominal voltage24 to 28 VDC (default setting: 24.5 V ±0.5%)
Power back immunity34 V
Protective functionsOutput is short-circuit, overload- and no-load proof.
Overvoltage protectionTyp. 36 V, max. 39 V
Efficiency, reliability
MTBF (reliability) / 2-phase operation525,000 h
MTBF (reliability) / 3-phase operation543,000 h
Efficiency/Loss / 2-phase operationTyp. 90.9% / PV = 24.5 W (400 V)
Efficiency/Loss / 3-phase operationTyp. 91.2% / PV = 23.6 W (400 V) Typ. 92% / PV = 21.4 W (500 V)
Ambient conditions
Temperature / Operation0 to 70°C
Temperature / Storage-25 to 85°C
Relative humidity / OperationMax. 95%
Mechanical properties
Dimensions / Width89 mm
Dimensions / Height124 mm
Dimensions / Depth117 mm (plus top-hat rail)
InstallationEasy snap-on mounting onto the top-hat rail
Weight980 g
Ventilation/CoolingNormal convection, no fan required

Documentation & CAD