IAC

B&R 0PS3201.3

Minimum space requirement in the control cabinet due to a thin design Robust and reliable thanks to dynamic boost with a strong output characteristic curve for starting heavy loads Optical and preventive function monitoring with three-color LED and dry switching contact Easy handling due to push-in connections, label fields, wire stripping mark and tamper-resistant setup Can be connected in parallel for increased power and redundancy Temperature range: -25°C to +70°C Worldwide use thanks to AC and DC wide-range input International certification package 48 VDC power supply unit, 3-phase, 20 A, input 400 to 500 VAC, wide range, thin design, top-hat rail installation

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

General information
Insulation voltages / Input - Output6 kV DC (type test) 3.1 kV DC (routine test)
Insulation voltages / Input - Ground4 kV DC (type test) 3.1 kV DC (routine test)
Insulation voltages / Input - Signal6 kV DC (type test) 3.1 kV DC (routine test)
Certifications / CEYes
Certifications / UKCAYes
Certifications / ULcULus E534663 Industrial control equipment
Status displayGreen LED (DC OK), threshold value Uout > 36 V
Active DC OK switch outputSee section "Dry switching contact".
Connection typePush-in connection
Input
Nominal input voltage400 to 500 VAC
Input voltage3x 400 to 500 VAC -20% to +10% 2x 400 to 500 VAC ±10%
Network typeStar network (TN, TT, IT(PE))
Frequency50 to 60 Hz
Inrush current<21 A
Current consumption3x 1.5 A / 3x 1.2 A (3x 400/500 VAC) 2x 2.6 A / 2x 2.1 A (2x 400/500 VAC)
I²t<0.94 A²s
Power failure bypassTyp. 34 ms (3x 400 VAC) Typ. 34 ms (3x 480 VAC)
Leakage current to PE<3.5 mA
Protective circuitVaristor transient protection
Internal fuse6.3 A
Required line fuse for device and line protectionSee section "Input protection".
Output
Nominal voltage48 VDC
Output power960 W / Max. 1440 W (5 s)
Output voltage40 to 56 VDC
Output current20 A / Max. 30 A (5 s)
Setting range for output voltage40 to 56 VDC
Control deviation<0.1% (input voltage change ±10%) <3% (load change, dynamic) <1% (load change, static)
Rise time≤1 s (UOUT (10 to 90%))
Residual rippleTyp. 50 mVSS
Can be connected in parallelYes, for increased efficiency and redundancy
Can be connected in seriesYes, for increased output voltage (observe SELV limit)
Overvoltage protection≤60 VDC (on the output (OVP))
Protective functionsShort-circuit protection
Feedback voltage resistance≤60 VDC
Efficiency, reliability
Power dissipation / Rated load<43.21 W (3x 400 VAC) <35.65 W (3x 480 VAC)
Power dissipation / No-load operation<0.3 W (3x 400 VAC) <0.26 W (3x 480 VAC)
EfficiencyTyp. 96.1% (3x 400 VAC) Typ. 96.3% (3x 480 VAC)
MTBF3x 480 VAC / >1,100,000 h (25°C) 3x 480 VAC / >660,000 h (40°C) 3x 480 VAC / >270,000 h (60°C)
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / Maximum5000 m
Flammability classV0
Ventilation/CoolingNormal convection, no fan required
Degree of protection per EN 60529IP20
Protection classI
Ambient conditions
Temperature / Operation-25 to 70°C
Temperature / DeratingSee section "Derating".
Temperature / Starting temperature-40°C
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationMax. 95%, non-condensing
Vibration / Operation10 to 50 Hz, amplitude ±0.2 mm 50 to 150 Hz, 2.3 g, 90 min, per IEC 60068-2-6
Shock / Operation18 ms, 30 g, in each direction, per IEC 60068-2-27
Pollution degree2
Climate category3K3, per EN 60721
Overvoltage categoryIII (≤2000 m) / II (≤5000 m), per EN 61010-1 III (≤2000 m) / II (≤5000 m), per EN 61010-2-201 II (≤ 2000 m) / II (≤ 5000 m), per EN 62368-1
Mechanical properties
Housing / MaterialAluminum sheet, plastic cover PA
Housing / CoatingNo protective coating
Dimensions / Width90 mm
Dimensions / Height135 mm
Dimensions / Depth167 mm
InstallationEasy top-hat rail installation (NS 35 rails, EN 60715)
Weight1938 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.