IAC

B&R 3AI780.6

2005 analog input module, 8 inputs, 0 to 20 mA, 16-bit, encoder power supply 24 VDC, single-channel isolated inputs and encoder power supply, order 2x TB718 terminal blocks separately!

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module8 analog inputs 0 to 25 mA
General information
Diagnostics / Module statusYes, using software
Diagnostics / Encoder power supplyYes, using LED status indicator and software
Diagnostics / I/O power supplyYes, using LED status indicator
Diagnostics / ConverterYes, using LED status indicator and software
Power consumption / Internal / 24 VDC-
Power consumption / Internal / 5 VDC1.5 W
Power consumption / Internal / Total1.5 W
Power consumption / I/O power supply14.0 W
Electrical isolation / Channel - ChannelYes (single-channel isolated)
Electrical isolation / Channel - PLCYes
Certifications / CEYes
Certifications / UKCAYes
Certifications / ULcULus E115267 Industrial control equipment
Status indicatorsConversion function sum monitoring, conversion function per channel, operating mode, filter time, encoder power supply per channel, module power supply per terminal block
Analog inputs
Encoder power supply / NoteA galvanically isolated encoder supply is generated from the encoder power supply for each channel.
Encoder power supply / VoltageModule power supply -15% / +25%
Encoder power supply / CurrentMax. 30 mA
Conversion time / Default mode20 ms at 50 Hz / 16.67 ms at 60 Hz
Conversion time / Trigger mode60 ms at 50 Hz / 50 ms at 60 Hz
Input0 to 25 mA
Input typeDifferential input
Digital converter resolution16-bit
Conversion timeFor all channels
Output formatINT
Load≤250 Ω
Input protectionProtection against wiring with supply voltage
Operating modesStandard mode (continuous mode), trigger mode
Basic accuracy±0.05% at 25°C
I/O power supply+24 VDC ±10% (+21.6 to +26.4 VDC)
Operating conditions
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation0 to 60°C
Temperature / Storage-25 to 70°C
Relative humidity / Operation5 to 95%
Mechanical properties
Dimensions / WidthSystem 2005 single-width
Can be installed on / Base unitYes
Can be installed on / Expansion unitYes
NoteOrder 2x terminal block TB718 separately.

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.