B&R 3DM486.6
2005 digital mixed module, 16 inputs 24 VDC, 1 ms, sink/source, 16 transistor outputs 24 VDC, 0.5 A, input and output group, electrically isolated, order 2x terminal blocks TB718 separately!
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 16 digital inputs, 16 digital outputs |
General information
| Diagnostics / Outputs | Yes, using LED status indicator and software |
| Diagnostics / Output monitoring | Yes, using LED status indicator and software |
| Diagnostics / I/O power supply | Yes, using LED status indicator and software |
| Power consumption / Internal / 24 VDC | - |
| Power consumption / Internal / 5 VDC | 1.2 W |
| Power consumption / Internal / Total | 1.2 W |
| Power consumption / External 24 V (DO) | 2.2 W |
| Electrical isolation / Group isolation | Input group - Output group |
| Electrical isolation / Channel - Channel | No |
| Electrical isolation / Channel - PLC | Yes |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Status indicators | I/O function per channel, I/O power supply for inputs and outputs, output monitoring |
Digital inputs
| Input filter / Hardware | ≤1 ms |
| Input filter / Software | - |
| Nominal voltage | 24 VDC |
| Input circuit | Sink or source |
Digital outputs
| Nominal voltage | 24 VDC |
| Nominal output current | 0.5 A |
| Total nominal current | 8.0 A |
| Output circuit | Source |
| Output protection | Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply |
| Sensor power supply | External |
Operating conditions
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature / Operation | 0 to 60°C |
| Temperature / Storage | -25 to 70°C |
| Relative humidity / Operation | 5 to 95% |
Mechanical properties
| Dimensions / Width | System 2005 single-width |
| Can be installed on / Base unit | Yes |
| Can be installed on / Expansion unit | Yes |
| Note | Order 2x TB718 terminal blocks separately |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.