B&R 3NC150.6
2005 counter module, 2 inputs for incremental encoder, 32-bit, input frequency 100 kHz, encoder power supply 5 to 30 VDC, 2 analog outputs ±10 V, 12-bit, 8-pin terminal block included in delivery!
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 2 counter channels, 2 analog outputs |
General information
| Diagnostics / Compensation current | Yes, using LED status indicator and software |
| Diagnostics / Homing | Yes, using LED status indicator and software |
| Power consumption / 24 VDC | 3.5 W |
| Power consumption / 5 VDC | 1.5 W |
| Power consumption / Total | 5.0 W |
| Electrical isolation / Output - Output | No |
| Electrical isolation / Output - Encoder | Yes |
| Electrical isolation / Output - PLC | Yes |
| Electrical isolation / Encoder - Encoder | No |
| Electrical isolation / Encoder - PLC | Yes |
| Certifications / CE | Yes |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Status indicators | Counter up/down, referencing, equipotential bonding current between analog outputs |
Counter channels
| Execution | Two 9-pin female DSUB connectors |
| Evaluation | 1x, 2x, 4x |
| Operating modes | Incremental or up/down counter configurable using software |
| Input filter | 2 times configurable using software |
| Input frequency | Max. 100 kHz |
| Encoder inputs | Symmetrical and asymmetrical |
| Encoder power supply | 5 to 30 V external |
| Counter size | 32-bit |
Analog outputs
| Output | ±10 V |
| Digital converter resolution | 12-bit |
| Conversion time | 35 µs for all outputs |
| Output protection | Short-circuit proof |
| Basic accuracy | ±0.5% at 20°C |
Operating conditions
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature / Operation | 0 to 60°C |
| Temperature / Storage | -25 to 70°C |
| Relative humidity / Operation | 5 to 95% |
Mechanical properties
| Dimensions / Width | System 2005 single-width |
| Can be installed on / Base unit | Yes |
| Can be installed on / Expansion unit | Yes |
| Note | 8-pole terminal block is included in delivery. |