IAC

B&R 4PP015.E420-101

Power Panel, 24 VDC, 153 x 120 mm, LCD display, 4 x 20 characters, Europe, backlight, 26 keys, 300 kB SRAM, 1984 kB FlashPROM, 1 RS232, 1 CAN interface network-capable, 16 digital inputs, 24 VDC, sink/source, 2 event counters or 1 incremental encoder or 2x gate/period measurement, 16 digital outputs, 24 VDC, 0.5 A source, IP65 protection (front), order 2x TB718, 1x TB103 terminal blocks separately!

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

General information
Diagnostics / I/O functionYes, using LEDs
Diagnostics / InterfaceYes, using LEDs
Diagnostics / StateYes, using LED status indicator
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)Evaluation ongoing
Certifications / ULcULus E115267 Industrial control equipment
Certifications / CE #2Yes
Status indicatorsI/O function per channel, status
Controller
Standard memory / System PROM448 kB FlashPROM
Standard memory / User PROM1984 kB FlashPROM
Standard memory / User RAM300 kB SRAM
Data bufferingLithium battery 3 V / 950 mAh
Real-time clockNonvolatile, resolution 1 s
Voltage monitoringAn NMI is triggered at a supply voltage of <15 VDC.
System bus for expansionsNo
Typical instruction cycle time0.8 µs
WatchdogYes
Display
Backlight / TypeLED
TypeMonochrome LCD
Resolution4 x 20 characters
Display character setEnglish/European
Interfaces
Interface IF1 / TypeRS232
Interface IF1 / Variant9-pin male DSUB connector
Interface IF1 / Electrical isolationNo
Interface IF1 / Max. baud rate115.2 kbit/s
Interface IF2 / TypeCAN
Interface IF2 / Variant9-pin male DSUB connector
Interface IF2 / Electrical isolationYes
Digital inputs
Electrical isolation / Group isolationNo
Electrical isolation / Channel - BusYes Yes
Electrical isolation / Channel - ChannelNo No
Quantity16
Nominal voltage24 VDC 24 VDC
Input circuitSink or source Sink or source
Input filter<10 μs, <1 ms
Additional functionsCounter -
Input current at nominal voltageApprox. 10 mA Approx. 5 mA
Channel1-3 4-6
Digital outputs
Electrical isolation / Group isolationNo
Electrical isolation / Channel - BusNo
Electrical isolation / Channel - ChannelNo
Nominal voltage24 VDC
Nominal output current0.5 A
Total nominal current8 A
Output circuitSource
Output protectionOverload protection, short-circuit protection
Internal protective circuitVDR
Keys
Function keys10 with LED (yellow)
Soft keysNo
System keysNumeric keys, cursor block
Label10 keys using slide-in labels
Power supply unit
Nominal voltage24 VDC
Power consumptionMax. 6 W
Operating conditions
Degree of protection per EN 60529IP65 (front)
Ambient conditions
Temperature / Operation0 to 50°C
Temperature / Storage-20 to 60°C
Relative humidity / Operation10 to 90%
Relative humidity / Storage5 to 95%
Mechanical properties
Dimensions / Width153 mm
Dimensions / Height120 mm
Dimensions / Depth46.1 mm
Weight0.5 kg

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.