IAC

B&R 4PP035.E300-36

Power Panel, 24 VDC, 153 x 120 mm, LCD display, 160 x 80 pixels, 3 inch, backlight, 26 keys, 300 kB SRAM, 1024 kB FlashPROM, 1 RS232, 1 CAN interface network-capable, 8 digital inputs, 24 VDC, sink/source, 2 event counters or 1 incremental encoder or 2x gate/period measurement, 8 digital outputs, 24 VDC, 0.5 A source, 4 analog inputs, ±10 V, 12-bit, two of the analog inputs can be used as KTY10 or Pt1000 inputs, 4 analog outputs, ±10 V, 12-bit, IP65 protection (front), order 2x TB718, 1x TB103 terminal blocks separately!

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

General information
Diagnostics / I/O functionYes, using LEDs
Diagnostics / InterfaceYes, using LEDs
Diagnostics / StateYes, using LED status indicator
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)Evaluation ongoing
Certifications / ULcULus E115267 Industrial control equipment
Certifications / CE #2Yes
Status indicatorsI/O function per channel, status
Controller
Standard memory / System PROM448 kB FlashPROM
Standard memory / User PROM1024 kB FlashPROM
Standard memory / User RAM300 kB SRAM
Data bufferingLithium battery 3 V / 950 mAh
Real-time clockNonvolatile, resolution 1 s
Voltage monitoringAn NMI is triggered at a supply voltage of <15 VDC.
System bus for expansionsNo
Typical instruction cycle time0.8 µs
WatchdogYes
Display
Backlight / TypeLED
TypeMonochrome LCD
Resolution160 x 80 pixels
Display character setEuropean/Cyrillic
Interfaces
Interface IF1 / TypeRS232
Interface IF1 / Execution9-pin male DSUB connector
Interface IF1 / Electrical isolationNo
Interface IF1 / Max. baud rate115.2 kbit/s
Digital inputs
Input filter / Channel 1-3<10 µs
Input filter / Channel 4-8<1 ms
Input current at nominal voltage / Channel 1-3Approx. 10 mA
Input current at nominal voltage / Channel 4-8Approx. 5 mA
Electrical isolation / Group isolationNo
Electrical isolation / Channel - BusYes
Electrical isolation / Channel - ChannelNo
Additional functions / Channel 1-3Counters
Additional functions / Channel 4-8-
Quantity8
Nominal voltage24 VDC
Input circuitSink or source
Analog inputs
Electrical isolation / Group isolationNo
Electrical isolation / Channel - BusYes
Electrical isolation / Channel - ChannelNo
Input filter / HardwareCutoff frequency 10 kHz / slope 60 dB
Input filter / Software-
Quantity4 differential inputs, 2 of which can be configured individually as temperature inputs
Input±10 V
Digital converter resolution12-bit
Conversion time150 µs for all channels
Output formatINT
Input impedance in signal range20 MΩ
Input circuitIEC 61131-2
Temperature measurement
Input filter / HardwareCutoff frequency 10 kHz / slope 60 dB
Input filter / Software-
Sensor / NoteConfigurable per channel
Sensor / KTY10-6-50 to 125°C
Sensor / Pt1000-200 to 850°C
Electrical isolation / Group isolationNo
Electrical isolation / Channel - BusYes
Electrical isolation / Channel - ChannelNo
QuantityUp to 2 (depends on the configuration)
Output formatINT
Digital converter resolution12-bit
InputResistance measurement in 2-wire method with constant current supply
Input circuitIEC 61131-2
Conversion time150 µs for all channels
Resistance measurement range0-4000 Ω
Digital outputs
Electrical isolation / Group isolationNo
Electrical isolation / Channel - BusNo
Electrical isolation / Channel - ChannelNo
Quantity8
Nominal voltage24 VDC
Nominal output current0.5 A
Total nominal current4 A
Output circuitSource
Output protectionOverload protection, short-circuit protection
Internal protective circuitVDR
Analog outputs
Electrical isolation / Group isolationNo
Electrical isolation / Channel - BusYes
Electrical isolation / Channel - ChannelNo
Quantity4
Output±10 V
Digital converter resolution12-bit
Conversion time150 µs for all channels
Switch on/off behaviorInternal enable relay for startup and errors
Output protectionSingle-channel continuous short circuit protection
Basic accuracy±0.088%
Keys
Function keys10 with LED (yellow)
Soft keysNo
System keysNumeric keys, cursor block
Label10 keys using slide-in labels
Power supply unit
Nominal voltage24 VDC
Power consumptionMax. 6 W
Operating conditions
Degree of protection per EN 60529IP65 (front)
Ambient conditions
Temperature / Operation0 to 50°C
Temperature / Storage-20 to 60°C
Relative humidity / Operation10 to 90%
Relative humidity / Storage5 to 95%
Mechanical properties
Dimensions / Width153 mm
Dimensions / Height120 mm
Dimensions / Depth46.1 mm
Weight0.5 kg

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.