IAC

B&R 8I44S200075.000-1

ACOPOSinverter S44, 1x 200-240 V, 0.75 kW, integrated EMC filter, RS485 interface

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

General information
Certifications / CEYes
Certifications / CRA (Cyber Resilience Act)Evaluation ongoing
Certifications / ULcULus E225616 Power conversion equipment
Certifications / KCYes
Motor power
Specified on nameplate0.75 kW 1 HP
Mains connection
Max. mains current / At 200 VAC10.2 A
Max. mains current / At 240 VAC8.5 A
Mains input voltage1x 200 VAC -15% to 240 VAC +10%
Frequency50 to 60 Hz ±5%
Apparent power (at 240 VAC)3.5 kVA
Max. assumed short-circuit current (Isc) (short-circuit current at connection point)1000 A
Power dissipation at max. output current44 W
Integrated EMC filterYes
Line-conducted and radiated emissions
With integrated filter / Motor cable length per IEC/EN 61800-3 Cat. C1 environment 1 (public power network)≤5 m
With integrated filter / Motor cable length per IEC/EN 61800-3 Cat. C2 environment 1 (public power network)≤5 m / ≤10 m
With integrated filter / Motor cable length per IEC/EN 61800-3 Cat. C3 environment 2 (industrial power system)≤5 m / ≤10 m
With add-on filter / Motor cable length per IEC/EN 61800-3 Cat. C1 environment 1 (public power network)≤20 m
With add-on filter / Motor cable length per IEC/EN 61800-3 Cat. C2 environment 1 (public power network)≤50 m
With add-on filter / Motor cable length per IEC/EN 61800-3 Cat. C3 environment 2 (industrial power system)≤50 m
With add-on filter8I0FS011.100-1
Motor connection
Derating of continuous output current depending on ambient temperature / Clock frequency 4 kHzNo derating (up to 40°C)
Derating of continuous output current depending on ambient temperature / Other clock frequenciesThe derating curves are included in the user's manual, which can be downloaded from www.br-automation.com.
Derating of continuous output current depending on installation elevation / Starting at 1000 m above sea level1%, per 100 m
Max. continuous output current (In) / At 240 VAC4.2 A
Nominal clock frequency / Min.2 kHz
Nominal clock frequency / Max.16 kHz
Max. motor cable length / Shielded cable50 m
Max. motor cable length / Non-shielded cable100 m
Max. transient current for 60 s6.3 A
Output frequency range0.5 to 400 Hz
Nominal clock frequency4 kHz
Braking torqueUp to 70% of the nominal motor torque without resistance
Motor control profilesStandard profile (voltage/frequency ratio - V/f characteristic curve) Power profile (flux vector control without encoder) Pump/Fan profile (quadratic characteristic curve Kn²)
Main protective functions of inverterThermal protection against overheating Protection against short circuits between motor phases Overcurrent protection between motor phases and ground Protection against overvoltage and undervoltage in the mains supply
Motor protectionThermal protection integrated in the inverter through continually calculating the l²t value
Short-term overload torque150 to 170% of the nominal motor torque depending on inverter power and motor type
Available internal power supplies
Output voltage 5 VDC / Max. output current at 5 VDC10 mA
Output voltage 24 VDC / Max. output current at 24 VDC100 mA
Output voltage 5 VDC5 VDC ±5%
Output voltage 24 VDC24 VDC -15% / +20%
Interfaces
TypeModbus RTU
Digital inputs
Electrical isolation / Input - ACOPOSinverterYes
Electrical isolation / Input - InputNo
Quantity4
Nominal voltage24 VDC
Input circuitSource or sink
Sampling time<20 ms ±1 ms
Input impedance3.5 kΩ
Analog inputs
Electrical isolation / Input - InputNo
Electrical isolation / Input - ACOPOSinverterYes
Input impedance / Voltage30 kΩ
Input impedance / Current250 Ω
Quantity1
Input0 to 5 V, 0 to 10 V or 0 to 20 mA
Resolution10-bit
Sampling time<10 ms
Digital outputs
Electrical isolation / Output - ACOPOSinverterYes
Electrical isolation / Output - OutputNo
Quantity1
Nominal voltage24 VDC
Output circuitSource or sink
Nominal output current10 mA (100 mA with external power supply)
Update time20 ms ±1 ms
Relay outputs
Switching capacity / Max. / With resistive load (cos φ = 1 and L/R = 0 ms)4 A at 30 VDC / 3 A at 250 VAC
Switching capacity / Max. / With inductive load (cos φ = 0.4 and L/R = 7 ms)2 A at 30 VDC or 250 VAC
Switching capacity / Min.5 mA for 24 VDC
Electrical isolation / Output - ACOPOSinverterYes
Electrical isolation / Output - OutputNo
Quantity1
Execution1 NO contact and 1 NC contact with a common point
Nominal voltage30 VDC / 250 VAC
Response time (max.)30 ms
Analog outputs
Electrical isolation / Output - ACOPOSinverterYes
Electrical isolation / Output - OutputNo
Max. load impedance / Voltage470 Ω
Max. load impedance / Current800 Ω
Quantity1
Output0 to 10 V or 0 to 20 mA
Update time<10 ms
Resolution8-bit
Operating conditions
Installation elevation above sea level0 to 1000 m
Degree of protection per EN 60529IP20
Ambient temperature-10 to 40°C
Max. ambient temperatureUp to +60°C
Relative humidity per IEC 60068-2-35 to 95%, non-condensing No dripping water
Maximum installation elevationUp to 2000 m
Max. pollution degree per IEC/EN 61800-5-12 (non-conductive pollution)
Ambient conditions per IEC 60721-3-3Class 3C3 and 3S2
Operating positionVertical mounting orientation ±10%
Ambient conditions
Temperature / Storage-25 to 70°C
Mechanical properties
Dimensions / Width72 mm
Dimensions / Height130 mm
Dimensions / Depth131.2 mm
Weight0.8 kg

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.