B&R 8I86T401100.00-000
Base device for ACOPOSinverter P86, 3x 380 to 480 V, 11 kW, EMC filter and brake chopper. Order number - ACOPOSinverter P86: 8I86T401100.0P-100: Inverter with POWERLINK communication card
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
General information
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| Certifications / UL | cULus E225616 Power conversion equipment |
Motor power
| Specified on nameplate | 11 kW (15 HP) |
Mains connection
| Max. mains current with optional mains choke / At 380 VAC | 21.9 A |
| Max. mains current with optional mains choke / At 480 VAC | 17.7 A |
| Mains current / At 380 VAC | 34.7 A |
| Mains current / At 480 VAC | 27.7 A |
| Power dissipation / External cooling | 313 W |
| Power dissipation / Natural cooling | 50 W |
| Mains input voltage | 3x 380 VAC -15% to 480 VAC +10% |
| Frequency | 50 to 60 Hz ±5% |
| Apparent power (at 480 VAC) | 23 kVA |
| Max. assumed short-circuit current (Isc) (short-circuit current at connection point) | 22 kA |
| Inrush current | Max. 80.8 A |
| Integrated EMC filter | Yes |
Line-conducted and radiated emissions
| With integrated filter / Motor cable length per IEC/EN 61800-3 Cat. C2 environment 1 (public power network) | - |
| With integrated filter / Motor cable length per IEC/EN 61800-3 Cat. C3 environment 2 (industrial power system) | 20 m |
| With add-on filter / Motor cable length per IEC/EN 61800-3 Cat. C1 environment 1 (public power network) | - |
| With add-on filter / Motor cable length per IEC/EN 61800-3 Cat. C2 environment 1 (public power network) | C2 level at 4 kHz with 50 m cable |
| With add-on filter / Motor cable length per IEC/EN 61800-3 Cat. C3 environment 2 (industrial power system) | C3 level at 4 kHz with 100 m cable |
| With add-on filter | 8I0FT050.200-1 |
Motor connection
| Derating of continuous output current depending on ambient temperature / At nominal clock frequency (4 kHz or 2.5 kHz with higher inverter power) | No derating (up to 50°C) |
| Derating of continuous output current depending on ambient temperature / Other clock frequencies | The derating curves are included in the installation instructions, which can be downloaded from www.br-automation.com. |
| Derating of continuous output current depending on installation elevation / Starting at 1000 m above sea level | 1%, per 100 m |
| Clock frequency / Min. | 2 kHz |
| Clock frequency / Max. | 16 kHz |
| Max. motor cable length / Shielded cable | 150 m |
| Max. motor cable length / Non-shielded cable | 300 m |
| Motor control profiles / Induction motor | Sensorless vector control: 1. Voltage controlled with constant torque → Default mode 2. Voltage controlled with variable torque → Energy-saving mode, e.g. for fans and pumps Vector control with encoder: 1. Current-controlled with constant torque → Default mode Sensorless slip control: 1. With V/f characteristic curve for constant torque → Default mode 2. With V/f characteristic curve for constant torque (up to 6 f ranges) → Mode for individual special applications 3. With V/f characteristic curve for quadratically increasing torque → Energy-saving mode, e.g. for fans and pumps |
| Motor control profiles / Synchronous motor | Sensorless vector control: 1. Voltage controlled with constant torque → Default mode Vector control with encoder: 1. Current-controlled with constant torque → Default mode |
| Nominal output current | 24 A |
| Max. transient current for 60 s | 36 A |
| Max. transient current for 2 s | 43 A |
| Output frequency range | 0.1 to 599 Hz |
| Nominal clock frequency | 4 kHz |
| Main protective functions of inverter | Thermal protection against power stage overheating Protection against short circuits between motor phases, overcurrent between output phases and ground, overvoltages on the DC bus, exceeding the speed limit. Safety function for: Overvoltage and undervoltage of the mains supply, mains phase failure with 3-phase power supply |
Brake chopper
| Integrated dynamic brake transistors | Yes |
| Min. resistance value (external) | 16 Ω |
24 VDC power supply
| Input voltage | 24 VDC (min. 20.4 VDC, max. 27 VDC) |
| Current | Max. 0.8 A |
Available internal power supplies
| Output voltage 24 VDC / Max. output current at 24 VDC | Max. 200 mA |
| Output voltage 10 VDC / Max. output current at 10 VDC | Max. 10 mA |
| Output voltage 24 VDC | 24 VDC (min. 20.4 VDC, max. 27 VDC) |
| Output voltage 10 VDC | 10.5 VDC ±5% |
Interfaces
| POWERLINK / Type | Type 3 |
Digital inputs
| Switching threshold / Low | Source: <0.5 V Sink: >16 V |
| Switching threshold / High | Source: >11 V Sink: <10 V |
| Electrical isolation / Input - ACOPOSinverter | Yes |
| Electrical isolation / Input - Input | No |
| Quantity | 5 |
| Nominal voltage | 24 VDC (max. 30 VDC) |
| Input circuit | Source or sink |
| Sampling time | 2 ms ±0.5 ms |
| Input impedance | 4.4 kΩ |
Safe input - STO (Safe Torque Off)
| Switching threshold / Low | <5 V |
| Switching threshold / High | >11 V |
| Electrical isolation / Input - ACOPOSinverter | Yes |
| Electrical isolation / Input - Input | No |
| Quantity | 2 |
| Nominal voltage | 24 VDC (max. 30 VDC) |
| Input impedance | 2.2 kΩ |
| Input circuit | Source |
Event counters
| Switching threshold / Low | <0.6 V |
| Switching threshold / High | >2.5 V |
| Quantity | 1 |
| Nominal voltage | 24 VDC (max. 30 VDC) |
| Input frequency | 0 to 30 kHz |
| Input circuit | Source |
| Sampling time | 5 ms ±1 ms |
Analog inputs
| Electrical isolation / Input - Input | No |
| Electrical isolation / Input - ACOPOSinverter | Yes |
| Input / Voltage | AI1: 0 to 10 VDC AI2: -10 to 10 VDC |
| Input / Current | AI1: 0 to 20 mA |
| Input impedance / Voltage | AI1: 31.5 kΩ AI2: 20 kΩ |
| Input impedance / Current | 250 Ω |
| Quantity | 2 |
| Nonlinearity | ±0.15% |
| Basic accuracy | ±0.6% with temperature fluctuation of 60°C |
| Resolution | 12-bit |
| Sampling time | 1 ms ±1 ms |
Digital outputs
| Quantity | 2 |
| Nominal voltage | 24 VDC -15%/+20% |
| Max. voltage | 30 VDC |
| Output circuit | Source or sink |
| Sampling time | 2 ms ±0.5 ms |
| Max. current | 100 mA |
Relay outputs
| Execution / Relay 1 | 1 changeover contact |
| Execution / Relay 2 | 1 normally open contact |
| Electrical isolation / Output - ACOPOSinverter | Yes |
| Electrical isolation / Output - Output | No |
| Quantity | 2 |
| Nominal voltage | 30 VDC / 250 VAC |
| Switching current range | Min. switching current: 5 mA at 24 VDC Max. switching current: R1: At cos φ = 1: Max. 3 A / At cos φ = 0.4: Max. 2 A R2: At cos φ = 1: Max. 5 A / At cos φ = 0.4: Max. 2 A |
| Response time (max.) | 5 ms ±0.5 ms |
Analog outputs
| Electrical isolation / Output - ACOPOSinverter | Yes |
| Electrical isolation / Output - Output | No |
| Max. load impedance / Voltage | 470 Ω |
| Max. load impedance / Current | 500 Ω |
| Quantity | 1 |
| Output | 0 to 10 VDC or 0 to 20 mA |
| Nonlinearity | ±0.2% |
| Basic accuracy | ±1% with temperature fluctuation of 60°C |
| Sampling time | 5 ms ±1 ms |
| Resolution | 10-bit |
Electrical properties
| Energy efficiency (IE classification) / Power dissipation relative to continuous apparent power | IE2 (10, 25): 0.7% (3x 380 VAC), 0.5% (3x 480 VAC) IE2 (50, 25): 0.6% (3x 380 VAC), 0.5% (3x 480 VAC) IE2 (10, 50): 0.9% (3x 380 VAC), 0.7% (3x 480 VAC) IE2 (50, 50): 0.8% (3x 380 VAC), 0.7% (3x 480 VAC) IE2 (90, 50): 1% (3x 380 VAC), 0.9% (3x 480 VAC) IE2 (10, 100): 1.6% (3x 380 VAC), 1.3% (3x 480 VAC) IE2 (50, 100): 1.5% (3x 380 VAC), 1.3% (3x 480 VAC) IE2 (90, 100): 1.9% (3x 380 VAC), 1.7% (3x 480 VAC) |
| Energy efficiency (IE classification) / Nominal losses in standby mode | 17 W (3x 380 VAC), 19 W (3x 480 VAC) |
Operating conditions
| Degree of protection per EN 61800-5-1 | IP20 |
| Degree of protection per EN 60529 | IP20 |
| Max. relative humidity per EN/IEC 60721-3-3 class 3K3 | 5 to 95%, non-condensing |
| Maximum installation elevation | ≤1000 m without derating 1000 to 3000 m with Derating |
| Max. pollution degree per IEC/EN 61800-5-1 | 2 (non-conductive pollution) |
| Ambient conditions per IEC 60721-3-3 | Class 3C3 and 3S3 |
| Operating position | Vertical mounting orientation ±10° |
Ambient conditions
| Temperature / Operation | -15 to 50°C without derating 50 to 60°C with derating |
| Temperature / Storage | -40 to 70°C |
| Max. vibration resistance | 1 gn 9 to 200 Hz EN/IEC 60721-3-3 class 3M3 1.5 mm peak to peak 2 to 19 Hz EN/IEC 60721-3-3 class 3M3 |
| Max. shock resistance | 15 gn (duration = 11 ms) per EN/IEC 60721-3-3 class 3M3 |
Mechanical properties
| Dimensions / Width | 180 mm |
| Dimensions / Height | 385 mm |
| Dimensions / Depth | 249 mm |
| Weight | 9.5 kg |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
3D CAD models
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.