B&R VCA0Y0200
- POWERLINK hybrid cable - 20.0 m - Not recommended for new projects
Lifecycle & replacement
Lifecycle status not indexed
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| Accessories | POWERLINK hybrid cable, M12, Y-coded |
General information
| Cable cross section | ((4x 0.15 mm²) + (4x 0.6 mm²)) |
| Durability | Flame-retardant per UL 1581, section 1061 Oil-resistant per IEC 60811-2-1 and VDE 0282 part 10 |
| Certification | CE |
Cable construction
| Supply lines / Quantity | 4 |
| Supply lines / Wire insulation | PP |
| Supply lines / Wire colors | White, blue, red, black |
| Supply lines / Variant | CuZn contact with Ni/Au contact surface |
| Supply lines / Cross section | 0.6 mm² |
| Signal line / Quantity | 4 |
| Signal line / Wire insulation | PP |
| Signal line / Wire colors | White/Orange, orange, white/green, green |
| Signal line / Variant | CuZn contact with Ni/Au contact surface |
| Signal line / Cross section | 0.15 mm² |
| Outer jacket / Material | PUR (halogen-free, low-adhesive) |
| Outer jacket / Color | Black RAL 9005 |
| Outer jacket / Labeling | B&R material number, production week, country of production, UL E-file number |
| Cable stranding | Yes |
| Cable shield | Tinned copper wire braiding |
Connector
| Type | 2x M12 SPEEDCON, Y-coded, male |
| Mating cycles | At least 100 |
| Contacts | 8 (4 power supply and 4 signal contacts) |
Electrical properties
| Test voltage / Wire - Wire | 1500 V (50 Hz, 1 min.) |
| Test voltage / Wire - Shield | 1500 V (50 Hz, 1 min.) |
| Conductor resistance / Supply lines | Max. 34.6 Ω/km |
| Conductor resistance / Signal line | Max. 280 Ω/km |
| Nominal voltage | Max. 50 VDC (peak value) |
| Nominal current | 4 A power supply line 0.5 A signal line |
| Transfer properties | Category 5 / Class D up to 100 MHz per ISO/IEC 11801 |
| Transfer rate | 100 Mbit/s |
| Insulation resistance | ≥5 GΩ/km |
Operating conditions
| Degree of protection per EN 60529 / Cables | IP67 |
| Degree of protection per EN 60529 / M12 connector | IP67 (connected and screwed in) |
Ambient conditions
| Temperature / Fixed installation | -25 to 90°C (male M12 connector) -40 to 90°C (cable) |
| Temperature / Flexible installation | -25 to 90°C (male M12 connector) -30 to 70°C (cable) |
Mechanical properties
| Dimensions / Length | 20.0 m |
| Dimensions / Diameter | 7.6 ±0.2 mm |
| Bend radius / After installation | Min. 10 outer diameter |
| Bend radius / During installation | Min. 5 outer diameter |
| Drag chain data / Acceleration | 3 m/s² |
| Drag chain data / Flex cycles | 2,000,000 |
| Drag chain data / Velocity | 3 m/s |
| Weight | Approx. 1823 g |