IAC

B&R X20AO2438

2 analog current outputs HART protocol integration Support for HART variables Electrically isolated analog channels 16-bit digital converter resolution OSP mode NetTime timestamp: HART image The module is equipped with 2 current outputs with 16-bit digital converter resolution. It supports the HART communication standard for data transfer, parameter configuration and diagnostics. The 2 channels are electrically isolated from each other. The user can select between the 3 output ranges 4 to 20 mA, 0 to 20 mA and 0 to 24 mA.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module2 analog outputs 4 to 20 mA, 0 to 20 mA or 0 to 24 mA
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator and software
Diagnostics / HART linkYes, using LED status indicator and software
Diagnostics / HART errorYes, using LED status indicator and software
Power consumption / Bus0.05 W
Power consumption / Internal I/O1.65 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0xB3AA
Status indicatorsI/O function per channel, operating state, module status, HART
Additional power dissipation caused by actuators (resistive) [W]-
Analog outputs
Data output rate / With HART210 ms (default)
Data output rate / Analog1 ms without ramp
Max. error / Gain / 4 to 20 mA±0.025%
Max. error / Gain / 0 to 20 mA±0.022%
Max. error / Gain / 0 to 24 mA±0.02%
Max. error / Offset / 4 to 20 mA±0.025%
Max. error / Offset / 0 to 20 mA±0.022%
Max. error / Offset / 0 to 24 mA±0.02%
Output format / 4 to 20 mAINT 0x0000 to 0x7FFF / 1 LSB = 0x0001 = 488.281 nA
Output format / 0 to 20 mAINT 0x0000 to 0x7FFF / 1 LSB = 0x0001 = 610.352 nA UINT 0x0000 to 0xFFFF / 1 LSB = 0x0001 = 305.176 nA
Output format / 0 to 24 mAINT 0x0000 to 0x5DC0 / 1 LSB = 0x0001 = 1000 nA
Max. gain drift / 4 to 20 mA±0.0055%/°C
Max. gain drift / 0 to 20 mA±0.005%/°C
Max. gain drift / 0 to 24 mA±0.005%/°C
Max. offset drift / 4 to 20 mA±0.0035%/°C
Max. offset drift / 0 to 20 mA±0.002%/°C
Max. offset drift / 0 to 24 mA±0.002%/°C
Error caused by load change / 4 to 20 mA0.14%
Error caused by load change / 0 to 20 mA0.1%
Error caused by load change / 0 to 24 mA0.1%
Test voltage / Channel - Channel1000 VAC
Test voltage / Channel - Bus1000 VAC
Test voltage / Channel - Ground1000 VAC
Output4 to 20 mA, 0 to 20 mA or 0 to 24 mA configurable using software
Digital converter resolution16-bit
Settling time on output change over entire range2 ms to 20 s, configurable using software
Output protectionShort-circuit proof, overvoltage protection (up to 30 VDC)
Open-circuit detectionYes, using hardware and software
Data formatINT
Load per channelMax. 600 Ω
Short-circuit proofYes, continuous
Output filterActive second-order low-pass filter / Cutoff frequency 19 Hz Configurable slew rate
Nonlinearity<0.003%
HART
Multi-drop operation / PossibleYes
Multi-drop operation / StationsUp to 15
Transmission amplitude / Minimum400 mVpp
Transmission amplitude / Typical500 mVpp
Transmission amplitude / Maximum600 mVpp
Receiving amplitude / Minimum120 mVpp
Receiving amplitude / Maximum1500 mVpp
Transfer rate1200 bit/s
Operating frequencies1200 Hz / 2200 Hz
Burst operation possibleYes
Electrical properties
Electrical isolationChannel isolated from channel and bus
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm