B&R X20AO4622

4 analog outputs Either current or voltage signal possible 13-bit digital converter resolution X20 analog output module, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution

View on our store →

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module4 analog outputs ±10 V or 0 to 20 mA / 4 to 20 mA
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / Channel typeYes, using software
Power consumption / Bus0.01 W
Power consumption / Internal I/O1.8 W (Rev. ≥J0), 2.2 W (Rev. <J0)
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0x1BA3
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Analog outputs
Digital converter resolution / Voltage±12-bit
Digital converter resolution / Current12-bit
Max. error / Voltage / Gain±0.08%
Max. error / Voltage / Offset±0.05%
Max. error / Current / Gain±0.09%
Max. error / Current / Offset±0.05%
Output format / VoltageINT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
Output format / CurrentINT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Load per channel / VoltageMax. ±10 mA, load ≥1 kΩ
Load per channel / CurrentLoad max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0)
Max. gain drift / Voltage±0.015%/°C
Max. gain drift / Current±0.02%/°C
Max. offset drift / Voltage±0.032%/°C
Max. offset drift / Current±0.032%/°C
Error caused by load change / VoltageMax. 0.11%, from 10 MΩ → 1 kΩ, resistive
Error caused by load change / CurrentMax. 0.5%, from 1 Ω → 600 Ω, resistive
Output±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals
Max. output current10 mA at voltage >5 V 15 mA at voltage <5 V
Conversion time300 µs for all outputs
Settling time on output change over entire range500 µs
Switch on/off behaviorInternal enable relay for startup
Output protectionShort-circuit proof
Short-circuit proofCurrent limiting ±40 mA
Output filterFirst-order low-pass filter / cutoff frequency 10 kHz
Nonlinearity<0.007%
Insulation voltage between channel and bus500 Veff
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C (Rev. ≥ J0), 0 to 55°C (Rev. < J0)
Temperature / Operation / Vertical mounting orientation-25 to 50°C (Rev. ≥ J0), 0 to 50°C (Rev. < J0)
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.