IAC

B&R X20AT2311

2 inputs for resistance temperature measurement PT100 sensor Direct resistance measurement 4-wire measurement Configurable filter time The module is equipped with 2 inputs for PT100 4-line resistance temperature measurement.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module2 inputs for PT100 resistance temperature measurement
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / InputsYes, using LED status indicator and software
Power consumption / Bus0.35 W
Power consumption / Internal I/O0.85 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0xA4AA
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Resistance measurement temperature inputs
Conversion time / 1000 Hz filter1 ms for all inputs
Conversion time / 50 Hz filter20 ms for all inputs
Max. error at 25°C / Gain±0.0059%
Max. error at 25°C / Offset±0.0015%
Temperature measurement monitoring / Range undershoot0x80000001
Temperature measurement monitoring / Range overshoot0x7FFFFFFF
Temperature measurement monitoring / Open circuit0x7FFFFFFF
Temperature measurement monitoring / General fault0x80000000
Temperature measurement monitoring / Open inputs0x7FFFFFFF
Resistance measurement monitoring / Range undershoot0x80000001
Resistance measurement monitoring / Range overshoot0xFFFFFFFF
Resistance measurement monitoring / Open circuit0xFFFFFFFF
Resistance measurement monitoring / General fault0x80000000
InputResistance measurement with constant current supply for 4-wire connections
Digital converter resolution24-bit
Filter timeConfigurable between 1 ms and 400 ms
Conversion procedureSigma-delta
Output formatDINT or UDINT for resistance measurement
Temperature measurement range-200 to 850°C
Resistance measurement range0.5 to 390 Ω
Temperature sensor resolution1 LSB = 0.001°C
Resistance measurement resolution0.001 Ω
Input filterFirst-order low-pass filter / cutoff frequency 1050 Hz
Sensor standardEN 60751
Insulation voltage between channel and bus500 Veff
Insulation voltage between channel and channel500 Veff
Linearization methodInternal
Measuring current1 mA
Temperature sensor normalization-200.0 to 850.0°C
Reference1568 Ω ±0.1%
Permissible input signalShort-term max. 28.8 V
Max. gain drift±0.00065%/°C
Max. offset drift±0.000025%/°C
Nonlinearity<0.001%
Standardized range of values for resistance measurement0.5 Ω to 390 Ω
Electrical properties
Electrical isolationChannel isolated from channel and bus
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5 ⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.