4 inputs for resistance temperature measurement For NTC resistance type 10 kΩ Resistance measurement 0 to 200 kΩ Configurable measurement type per channel 2-wire measurement Configurable filter time This module is equipped with 4 inputs for NTC resistance temperature measurement (10 kΩ at 25°C). In addition, this module can measure resistance from 0 to 200 kΩ.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 4 inputs for NTC (10 kΩ) resistance temperature measurement |
General information
| Diagnostics / Module run/error | Yes, using LED status indicator and software |
| Diagnostics / Inputs | Yes, using LED status indicator and software |
| Cable specification / Cable type | Shielded twisted pair cable |
| Cable specification / Line capacitance | Max. 1 nF |
| Power consumption / Bus | 0.01 W |
| Power consumption / Internal I/O | 0.72 W |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| Certifications / ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Certifications / HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| B&R ID code | 0xEA85 |
| Status indicators | I/O function per channel, operating state, module status |
| Additional power dissipation caused by actuators (resistive) [W] | - |
Resistance measurement temperature inputs
| Conversion time / 1 channel | 20 ms with 50 Hz filter |
| Conversion time / 2 - 4 channels | 40 ms per channel with 50 Hz filter |
| Sensor / Sensor type | Configurable per channel |
| Sensor / NTC10K type 1 | Vishay: NTCLE100E3103GB0, B25/85 = 3977 |
| Sensor / NTC10K type 2 | Vishay: NTCLE413E2103F400L, B25/85 = 3435 |
| Max. error at 25°C / Gain | ±0.35% |
| Max. error at 25°C / Offset | ±0.004% |
| Temperature sensor normalization / NTC10K type 1 | -30.0 to 100.0°C |
| Temperature sensor normalization / NTC10K type 2 | -30.0 to 100.0°C |
| Temperature measurement monitoring / Range undershoot | 0x8001 |
| Temperature measurement monitoring / Range overshoot | 0x7FFF |
| Temperature measurement monitoring / Open circuit | 0x7FFF |
| Temperature measurement monitoring / General fault | 0x8000 |
| Temperature measurement monitoring / Open inputs | 0x7FFF |
| Resistance measurement monitoring / Range overshoot | 0xFFFF |
| Resistance measurement monitoring / Open circuit | 0xFFFF |
| Resistance measurement monitoring / General fault | 0xFFFF |
| Resistance measurement monitoring / Open inputs | 0xFFFF |
| Input | Resistance measurement with constant current supply for 2-wire connections |
| Digital converter resolution | 16-bit |
| Filter time | Configurable between 16.7 and 66.7 ms |
| Conversion procedure | Sigma-delta |
| Output format | INT or UINT for resistance measurement |
| Temperature measurement range | -30 to 100°C for NTC with 10 kΩ |
| Resistance measurement range | 0 to 200 kΩ |
| Temperature sensor resolution | 1 LSB = 0.1°C for NTC with 10 kΩ |
| Resistance measurement resolution | 5 Ω |
| Input filter | First-order low-pass filter / cutoff frequency 1.35 kHz |
| Insulation voltage between channel and bus | 500 Veff |
| Linearization method | Internal |
| Measuring current | 9.1 µA ±1.5% |
| Reference | 103,125 Ω ±0.1% |
| Permissible input signal | Short-term max. ±30 V |
| Max. gain drift | ±0.006%/°C |
| Max. offset drift | ±0.00009 %/°C |
| Nonlinearity | <0.15% |
| Standardized range of values for resistance measurement | 0 to 200,000 Ω |
| Crosstalk between channels | <-70 dB |
Electrical properties
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
Operating conditions
| Mounting orientation / Horizontal | Yes |
| Mounting orientation / Vertical | Yes |
| Installation elevation above sea level / 0 to 2000 m | No limitation |
| Installation elevation above sea level / >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature / Operation / Horizontal mounting orientation | -25 to 60°C |
| Temperature / Operation / Vertical mounting orientation | -25 to 50°C |
| Temperature / Derating | - |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
| Relative humidity / Operation | 5 to 95%, non-condensing |
| Relative humidity / Storage | 5 to 95%, non-condensing |
| Relative humidity / Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5⁺⁰.² mm |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
ECAD / EPLAN
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.