B&R X20ATA312
2 inputs for resistance temperature measurement PT100 sensor Direct resistance measurement as well 4-wire measurement Filter time can be configured NetTime timestamp: Moment of measurement The module is equipped with 2 inputs for PT100 4-line resistance temperature measurement.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 2 inputs for Pt100 resistance temperature measurement |
General information
| Diagnostics / Module run/error | Yes, using LED status indicator and software |
| Diagnostics / Inputs | Yes, using LED status indicator and software |
| Power consumption / Bus | 0.01 W |
| Power consumption / Internal I/O | 0.4 W |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| Certifications / ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Certifications / HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Certifications / DNV | Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| Certifications / CCS | Yes |
| Certifications / LR | ENV1 |
| Certifications / KR | Yes |
| Certifications / ABS | Yes |
| Certifications / BV | EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
| B&R ID code | 0xE0E4 |
| Status indicators | I/O function per channel, operating state, module status |
| Additional power dissipation caused by actuators (resistive) [W] | - |
Resistance measurement temperature inputs
| Conversion time / 1 channel | 20 ms with 50 Hz filter |
| Conversion time / 2 channels | 40 ms per channel with 50 Hz filter |
| Max. error at 25°C / Gain | ±0.0059% |
| Max. error at 25°C / Offset | ±0.0015% |
| Temperature measurement monitoring / Range undershoot | 0x80000001 |
| Temperature measurement monitoring / Range overshoot | 0x7FFFFFFF |
| Temperature measurement monitoring / Open circuit | 0x7FFFFFFF |
| Temperature measurement monitoring / General fault | 0x80000000 |
| Temperature measurement monitoring / Open inputs | 0x7FFFFFFF |
| Resistance measurement monitoring / Range undershoot | 0x80000001 |
| Resistance measurement monitoring / Range overshoot | 0xFFFFFFFF |
| Resistance measurement monitoring / Open circuit | 0xFFFFFFFF |
| Resistance measurement monitoring / General fault | 0x80000000 |
| Input | Resistance measurement with constant current supply for 4-wire connections |
| Digital converter resolution | 24-bit |
| Filter time | Configurable between 1 and 200 ms |
| Conversion procedure | Sigma-delta |
| Output format | DINT or UDINT for resistance measurement |
| Temperature measurement range | -200 to 850°C |
| Resistance measurement range | 0.5 to 390 Ω |
| Temperature sensor resolution | 1 LSB = 0.01°C |
| Resistance measurement resolution | 0.001 Ω |
| Input filter | First-order low-pass filter / cutoff frequency 1050 Hz |
| Sensor standard | EN 60751 |
| Insulation voltage between channel and bus | 500 Veff |
| Linearization method | Internal |
| Measuring current | 1 mA |
| Temperature sensor normalization | -200.0 to 850.0°C |
| Reference | 1568 Ω ±0.1% |
| Permissible input signal | Short-term max. 28.8 V |
| Max. gain drift | ±0.00065%/°C |
| Max. offset drift | ±0.000025%/°C |
| Nonlinearity | <0.001% |
| Standardized range of values for resistance measurement | 19 to 390 Ω |
Electrical properties
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
Operating conditions
| Mounting orientation / Horizontal | Yes |
| Mounting orientation / Vertical | Yes |
| Installation elevation above sea level / 0 to 2000 m | No limitation |
| Installation elevation above sea level / >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature / Operation / Horizontal mounting orientation | -25 to 60°C |
| Temperature / Operation / Vertical mounting orientation | -25 to 50°C |
| Temperature / Derating | - |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
| Relative humidity / Operation | 5 to 95%, non-condensing |
| Relative humidity / Storage | 5 to 95%, non-condensing |
| Relative humidity / Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order 1x terminal block X20TB1F separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5⁺⁰.² mm |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
ECAD / EPLAN
Certificates
- 2226379 CSA Certificate of Compliance X20 X67
- 64331_A1 BV Certificate of Compliance X20
- 64331_A1 BV Certificate of Compliance X20(de)
- CCS Type Approval Certificate - X20
- E115267 UL Certificate of Compliance X20
- EU Data Act - X20 IO - Connected Product Information Notice
- EU Declaration ATEX X20
- EU Declaration of conformity PLC X20
- FTZU 09 ATEX 0083X
- KR Type Approval Certificate MIL39390-AC003 (X20 System)
- Lloyds Register (X20 only)
- TAA00000BJ DNV Type Approval Certificate X20
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.