Single-channel electrical isolation Integrated terminal temperature compensation 2x PT1000 sensor integrated in the terminal 2x external PT1000 sensor can be connected, 2-wire or 4-wire connections NetTime timestamp: Moment of measurement The module is equipped with 2 inputs for J, K, N, S, B, R, E, C and T thermocouple sensors. The 2 measurement channels are electrically isolated from each other. This module can also be equipped with the X20TB1E thermocouple terminal block with integrated PT1000 temperature sensors. This makes it possible to achieve optimal terminal temperature compensation.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module2 inputs for thermocouples
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / InputsYes, using LED status indicator and software
Power consumption / Bus0.35 W
Power consumption / Internal I/O0.5 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0xBB98
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Thermocouple temperature inputs
Conversion time / Internal terminal temperature comp.2 * 4 * x ms
Conversion time / External terminal temperature comp.x ms
Conversion time / Remote temperature comp.2 * 4 * x ms
Measurement range / Sensor temperature / Type J: Fe-CuNi-210 to 1200°C
Measurement range / Sensor temperature / Type K: NiCr-Ni-270 to 1372°C
Measurement range / Sensor temperature / Type N: NiCrSi-NiSi-270 to 1298°C
Measurement range / Sensor temperature / Type S: PtRh10-Pt-50 to 1768°C
Measurement range / Sensor temperature / Type B: PtRh30-PtRh60 to 1820°C
Measurement range / Sensor temperature / Type R: PtRh13-Pt-50 to 1760°C
Measurement range / Sensor temperature / Type E: NiCr-CuNi-270 to 997°C
Measurement range / Sensor temperature / Type C: WRe5-WRe260 to 2310°C
Measurement range / Sensor temperature / Type T: Cu-CuNi-270 to 400°C
Measurement range / Terminal temperature-40 to 130°C
Measurement range / Voltage±65.534 mV
Resolution / Sensor temperature1 LSB = 0.1°C
Resolution / Terminal temperature1 LSB = 0.1°C
Resolution / VoltageDepending on gain, 1 LSB = 1 µV or 2 µV
Normalization / Type J: Fe-CuNi-210.0 to 1200.0°C
Normalization / Type K: NiCr-Ni-270.0 to 1372.0°C
Normalization / Type N: NiCrSi-NiSi-270.0 to 1298.0°C
Normalization / Type S: PtRh10-Pt-50.0 to 1768.0°C
Normalization / Type B: PtRh30-PtRh60 to 1820.0°C
Normalization / Type R: PtRh13-Pt-50.0 to 1760.0°C
Normalization / Type E: NiCr-CuNi-270.0 to 997.0°C
Normalization / Type C: WRe5-WRe260 to 2310.0°C
Normalization / Type T: Cu-CuNi-270.0 to 400.0°C
Normalization / Terminal temperature (Pt1000)-40.0 to 130.0°C
Normalization / VoltageDepending on gain ±32.767 mV or ±65.534 mV
Monitoring / Range undershoot0x8001
Monitoring / Range overshoot0x7FFF
Monitoring / Open circuit0x7FFF
Monitoring / Open inputs0x7FFF
Monitoring / General fault0x8000
Max. error at 25°C / Offset / Type J: Fe-CuNi±0.03%
Max. error at 25°C / Offset / Type K: NiCr-Ni±0.04%
Max. error at 25°C / Offset / Type N: NiCrSi-NiSi±0.04%
Max. error at 25°C / Offset / Type S: PtRh10-Pt±0.1%
Max. error at 25°C / Offset / Type B: PtRh30-PtRh6±0.12%
Max. error at 25°C / Offset / Type R: PtRh13-Pt±0.08%
Max. error at 25°C / Offset / Type E: NiCr-CuNi±0.03%
Max. error at 25°C / Offset / Type C: WRe5-WRe26±0.05%
Max. error at 25°C / Offset / Type T: Cu-CuNi±0.08%
Max. error at 25°C / Offset / Voltage±0.017%
Max. error at 25°C / Gain±0.07%
Max. gain drift / Channel±0.01%/°C
Max. gain drift / Terminal temperature (Pt1000)±0.003 %/°C
Max. offset drift / Type J: Fe-CuNi±0.0019 %/°C
Max. offset drift / Type K: NiCr-Ni±0.0025 %/°C
Max. offset drift / Type N: NiCrSi-NiSi±0.003 %/°C
Max. offset drift / Type S: PtRh10-Pt±0.0081 %/°C
Max. offset drift / Type B: PtRh30-PtRh6±0.0111 %/°C
Max. offset drift / Type R: PtRh13-Pt±0.0072 %/°C
Max. offset drift / Type E: NiCr-CuNi±0.0017 %/°C
Max. offset drift / Type C: WRe5-WRe26±0.0039 %/°C
Max. offset drift / Type T: Cu-CuNi±0.0072 %/°C
Max. offset drift / Terminal temperature (Pt1000)±0.005 %/°C
Max. offset drift / Voltage±0.001%/°C
Nonlinearity / Channel±0.004%
Nonlinearity / Terminal temperature±0.004%
Terminal temperature compensation / Accuracy of internal terminal temperature / With natural convection±1.5°C after 20 min
Terminal temperature compensation / Accuracy of internal terminal temperature / With artificial convection±3°C after 20 min
Terminal temperature compensation / Operating modesInternal/remote or external
Terminal temperature compensation / Basic accuracy at 25°C not taking Pt1000 sensor into account±0.06%
Common-mode rejection / DC>110 dB
Common-mode rejection / 50 Hz>110 dB
Common-mode rejection / 60 Hz>110 dB
Insulation voltage / Between channel and bus500 Veff
Insulation voltage / Between channel and channel500 Veff
InputThermocouple
Digital converter resolution16-bit
Filter timeConfigurable between 1 ms and 200 ms
Output formatINT
Sensor standardEN 60584
Conversion procedureSigma-delta
Linearization methodInternal
Permissible input signalMax. ±5 V
Input filterFirst-order low-pass filter / cutoff frequency 500 Hz
Common-mode range±50 V
Crosstalk between channels<-70 dB
Electrical properties
Electrical isolationChannel isolated from channel and bus
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB1E for internal/remote terminal temperature compensation separately. Order 1x terminal block X20TB1F for external terminal temperature compensation separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm