| Conversion time / Internal terminal temperature comp. / N channels | (n + 2) * 4 * x ms |
| Conversion time / External terminal temperature comp. / 1 channel | x ms |
| Conversion time / External terminal temperature comp. / N channels | n * 4 * x ms |
| Conversion time / Remote temperature comp. / N channels | (n + 2) * 4 * x ms |
| Measurement range / Sensor temperature / Type J: Fe-CuNi | -210 to 1200°C |
| Measurement range / Sensor temperature / Type K: NiCr-Ni | -270 to 1372°C |
| Measurement range / Sensor temperature / Type N: NiCrSi-NiSi | -270 to 1298°C |
| Measurement range / Sensor temperature / Type S: PtRh10-Pt | -50 to 1768°C |
| Measurement range / Sensor temperature / Type B: PtRh30-PtRh6 | 0 to 1820°C |
| Measurement range / Sensor temperature / Type R: PtRh13-Pt | -50 to 1760°C |
| Measurement range / Sensor temperature / Type E: NiCr-CuNi | -270 to 997°C |
| Measurement range / Sensor temperature / Type C: WRe5-WRe26 | 0 to 2310°C |
| Measurement range / Sensor temperature / Type T: Cu-CuNi | -270 to 400°C |
| Measurement range / Terminal temperature | -40 to 130°C |
| Measurement range / Voltage | ±65.534 mV |
| Resolution / Sensor temperature | 1 LSB = 0.1°C or 0.01°C |
| Resolution / Terminal temperature | 1 LSB = 0.1°C or 0.01°C |
| Resolution / Voltage | Depending on gain, 1 LSB = 1 µV or 2 µV |
| Normalization / Type J: Fe-CuNi | -210.0 to 1200.0°C or -210.00 to 1200.00°C |
| Normalization / Type K: NiCr-Ni | -270.0 to 1372.0°C or -270.00 to 1372.00°C |
| Normalization / Type N: NiCrSi-NiSi | -270.0 to 1298.0°C or -270.00 to 1298.00°C |
| Normalization / Type S: PtRh10-Pt | -50.0 to 1768.0°C or -50.00 to 1768.00°C |
| Normalization / Type B: PtRh30-PtRh6 | 0 to 1820.0°C or 0 to 1820.00°C |
| Normalization / Type R: PtRh13-Pt | -50.0 to 1760.0°C or -50.00 to 1760.00°C |
| Normalization / Type E: NiCr-CuNi | -270.0 to 997.0°C or -270.00 to 997.00°C |
| Normalization / Type C: WRe5-WRe26 | 0 to 2310.0°C or 0 to 2310.00°C |
| Normalization / Type T: Cu-CuNi | -270.0 to 400.0°C or -270.00 to 400.00°C |
| Normalization / Terminal temperature | -145.0 to 840.0°C or -145.00 to 840.00°C |
| Normalization / Voltage | Depending on gain ±32.767 mV or ±65.534 mV |
| Monitoring / Range undershoot | 0x8001 or 0x80000001 |
| Monitoring / Range overshoot | 0x7FFF or 0x7FFFFFFF |
| Monitoring / Open circuit | 0x7FFF or 0x7FFFFFFF |
| Monitoring / Open inputs | 0x7FFF or 0x7FFFFFFF |
| Monitoring / General fault | 0x8000 or 0x80000000 |
| Max. error at 25°C / Offset / Type J: Fe-CuNi | ±0.06% |
| Max. error at 25°C / Offset / Type K: NiCr-Ni | ±0.07% |
| Max. error at 25°C / Offset / Type N: NiCrSi-NiSi | ±0.07% |
| Max. error at 25°C / Offset / Type S: PtRh10-Pt | ±0.13% |
| Max. error at 25°C / Offset / Type B: PtRh30-PtRh6 | ±0.15% |
| Max. error at 25°C / Offset / Type R: PtRh13-Pt | ±0.11% |
| Max. error at 25°C / Offset / Type E: NiCr-CuNi | ±0.06% |
| Max. error at 25°C / Offset / Type C: WRe5-WRe26 | ±0.08% |
| Max. error at 25°C / Offset / Type T: Cu-CuNi | ±0.11% |
| Max. error at 25°C / Offset / Voltage | ±0.015% |
| Max. error at 25°C / Gain | ±0.04% |
| Max. gain drift / Channel | ±0.01%/°C |
| Max. gain drift / Terminal temperature | ±0.03 %/°C |
| Max. offset drift / Type J: Fe-CuNi | ±0.0033 %/°C |
| Max. offset drift / Type K: NiCr-Ni | ±0.0042 %/°C |
| Max. offset drift / Type N: NiCrSi-NiSi | ±0.0048 %/°C |
| Max. offset drift / Type S: PtRh10-Pt | ±0.0123 %/°C |
| Max. offset drift / Type B: PtRh30-PtRh6 | ±0.0166 %/°C |
| Max. offset drift / Type R: PtRh13-Pt | ±0.0109 %/°C |
| Max. offset drift / Type E: NiCr-CuNi | ±0.003 %/°C |
| Max. offset drift / Type C: WRe5-WRe26 | ±0.0062 %/°C |
| Max. offset drift / Type T: Cu-CuNi | ±0.011%/°C |
| Max. offset drift / Terminal temperature | ±0.005 %/°C |
| Max. offset drift / Voltage | ±0.003 %/°C |
| Nonlinearity / Channel | ±0.004% |
| Nonlinearity / Terminal temperature | ±0.004% |
| Terminal temperature compensation / Accuracy of internal terminal temperature / With natural convection | ±1.5°C after 20 min |
| Terminal temperature compensation / Accuracy of internal terminal temperature / With artificial convection | ±3°C after 20 min |
| Terminal temperature compensation / Operating modes | Internal/remote or external |
| Terminal temperature compensation / Basic accuracy at 25°C not taking Pt1000 sensor into account | ±0.06% |
| Common-mode rejection / DC | >100 dB |
| Common-mode rejection / 50 Hz | >100 dB |
| Common-mode rejection / 60 Hz | >100 dB |
| Insulation voltage / Between channel and bus | 500 Veff |
| Input | Thermocouple |
| Digital converter resolution | 16-bit |
| Filter time | Configurable between 1 and 200 ms |
| Output format | INT |
| Sensor standard | EN 60584 |
| Conversion procedure | Sigma-delta |
| Linearization method | Internal |
| Permissible input signal | Max. ±15 V |
| Input filter | First-order low-pass filter / cutoff frequency 500 Hz |
| Common-mode range | ±14 V |
| Crosstalk between channels | <-70 dB |