B&R X20BC0043-10

Fieldbus: CANopen Auto-configuration of I/O modules I/O configuration via the fieldbus Constant response times even with large amounts of data (max. 32 Rx and 32 Tx PDOs) Configurable I/O cycle (0.5 to 4 ms) Configurable transfer rate or automatic transfer rate detection Heartbeat consumer and producer Emergency producer 2x SDO server, NMT slave Simple bootup (autostart) Terminal access via serial interface on the X20PS9400 Integrated terminating resistor Controller Area Network (CAN) is widespread in automation technology. CAN topology is based on a line structure and uses twisted wire pairs for data transfer. CANopen is a higher-layer protocol based on CAN. The standardized protocol offers very flexible configuration options. This bus controller makes it possible to connect up to 253 X2X Link I/O modules to CANopen. A transition between IP20 and IP67 protection is possible by directly connecting X20, X67 or XV modules to one another at distances of up to 100 m each across control cabinet boundaries as required. All CANopen operating modes such as synchronous, event and polling are supported as well as PDO linking, life/node guarding, heartbeat, emergency objects and much more. With multifunction modules, the bus controller supports only the default function model in the event of automatic configuration by the bus controller (see the respective module description). Automation Studio V4.3 or later can be used to easily create configuration files (e.g. DCF files). All other function models are also supported by transferring configuration data to the bus controller (e.g. via the master environment with an SDO download). Automation Studio can be downloaded at no cost from the B&R website (www.br-automation.com). The evaluation license is permitted to be used to create complete configurations for fieldbus bus controllers at no cost.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
Bus controllerCANopen slave
General information
Diagnostics / Module statusYes, using LED status indicator and software
Diagnostics / Bus functionYes, using LED status indicator and software
Diagnostics / Data transferYes, using LED status indicator
Diagnostics / Terminating resistorYes, using LED status indicator
Power consumption / Bus1.5 W (rev. <H0: 2 W)
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
B&R ID code0xA8B8
Status indicatorsModule status, bus function, data transfer, terminating resistor
Interfaces
Min. cycle time / FieldbusNo limitation
Min. cycle time / X2X Link500 μs
FieldbusCANopen slave
Variant5-pin male multipoint connector
Max. distance1000 m
Transfer rateMax. 1 Mbit/s
Default transfer rateAutomatic transfer rate detection or fixed setting
Synchronization between bus systems possibleNo
Terminating resistorIntegrated in module
Electrical properties
Electrical isolationCANopen isolated from I/O CANopen not isolated from bus
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block TB2105 separately. Order 1x terminal block X20TB12 separately. Order 1x power supply module X20PS9400 or X20PS9402 separately. Order 1x bus base X20BB80 separately.
Pitch37.5⁺⁰.² mm