1 full-bridge strain gauge input Data output rate configurable from 0.1 Hz to 7.5 kHz Special operating modes (synchronous mode and multiple sampling) Configurable filter level This module works with both 4-wire and 6-wire strain gauge load cells. The concept applied by the module requires compensation in the measurement system. This compensation eliminates the absolute uncertainty in the measurement circuit, such as component tolerances, effective bridge voltage or zero point offset. The measurement precision refers to the absolute (compensated) value, which will only change as a result of changes in the operating temperature.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module1 full-bridge strain gauge input
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / Open circuitYes, using LED status indicator and software
Diagnostics / InputYes, using LED status indicator and software
Power consumption / Bus0.01 W
Power consumption / Internal I/O0.5 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
B&R ID code0xEB00
Status indicatorsChannel status, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]Max. +0.36
Full-bridge strain gauge
Input filter / Cutoff frequency5 Hz
Input filter / Order3
Input filter / Slope60 dB
Output of digital value / Broken bridge supply lineValue approaching 0
Output of digital value / Broken sensor lineValue approaching ±end value (status bit "Line monitoring" is set in register "Module status")
Output of digital value / Valid range of values0xFF800001 to 0x007FFFFF (-8,388,607 to 8,388,607)
Strain gauge supply / Voltage5.5 VDC / Max. 65 mA
Strain gauge supply / Short-circuit and overload-proofYes
Strain gauge supply / Voltage drop for short-circuit protectionMax. 0.2 VDC at 65 mA and 25°C
Quantization / LSB value (16-bit) / 2 mV/V336 nV
Quantization / LSB value (16-bit) / 4 mV/V671 nV
Quantization / LSB value (16-bit) / 8 mV/V1.343 µV
Quantization / LSB value (16-bit) / 16 mV/V2.686 µV
Quantization / LSB value (16-bit) / 32 mV/V5.371 μV
Quantization / LSB value (16-bit) / 64 mV/V10.74 μV
Quantization / LSB value (16-bit) / 128 mV/V21.48 μV
Quantization / LSB value (16-bit) / 256 mV/V42.97 μV
Quantization / LSB value (24-bit) / 2 mV/V1.31 nV
Quantization / LSB value (24-bit) / 4 mV/V2.62 nV
Quantization / LSB value (24-bit) / 8 mV/V5.25 nV
Quantization / LSB value (24-bit) / 16 mV/V10.49 nV
Quantization / LSB value (24-bit) / 32 mV/V20.98 nV
Quantization / LSB value (24-bit) / 64 mV/V41.96 nV
Quantization / LSB value (24-bit) / 128 mV/V83.92 nV
Quantization / LSB value (24-bit) / 256 mV/V167.85 nV
Strain gauge factor2 to 256 mV/V, configurable using software
Connection4- or 6-wire connections
Input typeDifferential, used to evaluate a full-bridge strain gauge
Digital converter resolution24-bit
Conversion timeDepends on the configured data output rate
Data output rate0.1 - 7500 samples per second, configurable using software (fDATA)
ADC filter characteristicsSigma-delta, see section "Filter characteristics of the sigma-delta A/D converter"
Operating range / Measurement sensor85 to 5000 Ω
Influence of cable lengthSee section "Calculation example".
Input protectionRC protection
Common-mode range0 to 3 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on inputs "Input +" and "Input -"
Insulation voltage between input and bus500 Veff
Conversion procedureSigma-delta
Max. gain drift12 ppm/°C
Max. offset drift2 ppm/°C
Nonlinearity<10 ppm
Electrical properties
Electrical isolationBus isolated from analog input and strain gauge supply voltage Channel not isolated from I/O power supply
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Hardware configuration"
Temperature / Starting temperatureYes, -40°C
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationUp to 100%, condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20cBM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.