B&R X20cBC8083

POWERLINK I/O configuration and firmware update via the fieldbus Integrated hub for efficient cabling Up to 2 slots for hub expansion modules 2x/4x/6x Fast Ethernet hub The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler. POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org. The bus modules expanded to the left allow connection of up to 2 hub expansion modules in addition to the bus controller. Each expansion module is equipped with 2 RJ45 connections. This means that a basic device provides up to 6 hub connections.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
Bus controllerPOWERLINK (V1/V2) controlled node with up to 2 slots for hub expansion modules
General information
Diagnostics / Module statusYes, using LED status indicator and software
Diagnostics / Bus functionYes, using LED status indicator and software
Support / Dynamic node allocation (DNA)Yes
Power consumption / Bus2 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
B&R ID code0xE218
Status indicatorsModule status, bus function
Additional power dissipation caused by actuators (resistive) [W]-
Interfaces
Transfer / Physical layer100BASE-TX
Transfer / Half-duplexYes
Transfer / Full-duplexNo
Transfer / AutonegotiationYes
Transfer / Auto-MDI/MDIXYes
Min. cycle time / Fieldbus200 μs
Min. cycle time / X2X Link200 μs
FieldbusPOWERLINK (V1/V2) controlled node
TypeType 2
Variant2x shielded RJ45 (hub)
Line lengthMax. 100 m between 2 stations (segment length)
Transfer rate100 Mbit/s
Hub propagation delay0.96 to 1 µs
Synchronization between bus systems possibleYes
Electrical properties
Electrical isolationPOWERLINK isolated from bus and I/O
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Starting temperatureYes, -40°C
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationUp to 100%, condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
Pitch / X20BB8037.5⁺⁰.² mm
Pitch / X20BB8162.5⁺⁰.² mm
Pitch / X20BB8287.5⁺⁰.² mm
NoteOrder 1x terminal block X20TB12 separately. Order 1x power supply module X20cPS9400 separately. Order 1x bus base X20cBB8x separately.