IAC

B&R X20cDO6639

6 digital outputs Relay module for 240 VAC / 30 VDC Switching current 2 A 6 normally open contacts Single-channel isolated outputs This module is equipped with 6 relay outputs with normally open contacts for 240 VAC / 30 VDC. The outputs are single-channel isolated.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module6 digital outputs 30 VDC / 240 VAC, outputs single-channel isolated
General information
Diagnostics / Module run/errorYes, using LED status indicator
Diagnostics / OutputsYes, using LED status indicator
Power consumption / Bus1 W
Power consumption / Internal I/O-
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
B&R ID code0xE22A
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]+0.36
Digital outputs
Switching delay / 0 → 1≤10 ms
Switching delay / 1 → 0≤10 ms
Insulation voltages / Channel - BusTested at 2300 VAC
Insulation voltages / Channel - ChannelTested at 750 VAC
Service life / ElectricalMin. 120 x 10³ops. (at 2 A / 240 VAC)
Service life / MechanicalMin. 2 x 10⁷ ops
Switching capacity / Total power of all channels / AC3000 W
Switching capacity / Total power of all channels / DC360 W
Switching capacity / Minimum0.05 W DC / 2.4 W AC
Switching capacity / Maximum60 W DC / 480 W AC
Protective circuit / External / ACRC combination or VDR
Protective circuit / External / DCInverse diode, RC combination or VDR
Protective circuit / InternalNone
VariantRelay / Normally open contact Channels are single-channel isolated.
Nominal voltage30 VDC / 240 VAC
Max. voltage264 VAC
Switching voltageMax. 110 VDC / 264 VAC
Rated frequencyDC / 45 to 63 Hz
Nominal output current2 A at 30 VDC / 2 A at 240 VAC
Total nominal current10 A at 30 VDC / 10 A at 240 VAC
Actuator power supplyExternal
Contact resistanceMax. 100 mΩ
Electrical properties
Electrical isolationChannel isolated from bus and I/O power supply
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mNot permitted
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationUp to 100%, condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB32 separately, order 1x bus module X20cBM12 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.