IAC

B&R X20cDO8332

8 digital outputs with 2 A Source connection 1-wire connections Power feed integrated in the module Integrated output protection This module is equipped with 8 outputs for 1-wire connections. The outputs are designed for a source circuit. The nominal output current is 2 A. The output supply is fed directly to the module. An additional supply module is not needed. There is no connection between the module and the I/O supply potential on the bus module.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module8 digital outputs 24 VDC for 1-wire connections
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator and software (output error status)
Diagnostics / Supply voltage monitoringYes, using software
Power consumption / Bus0.22 W
Power consumption / Internal I/O-
Power consumption / External I/O0.92 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
B&R ID code0xE22C
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]+2.24
Digital outputs
Total nominal current / Per group4 A
Total nominal current / Per module8 A
Actuator power supply / SupplyExternal
Actuator power supply / FuseRequired line fuse: Max. 10 A, slow-blow
Switching delay / 0 → 1<300 µs
Switching delay / 1 → 0<300 µs
Switching frequency / Resistive loadMax. 500 Hz
Switching frequency / Inductive loadSee section "Switching inductive loads".
VariantCurrent-sourcing FET
Number of output groups2
Nominal voltage24 VDC
Switching voltage24 VDC -15% / +20%
Nominal output current2 A
Connection type1-wire connections
Output circuitSource
Output protectionThermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current") Internal freewheeling diode for switching inductive loads (see section "Switching inductive loads") Reverse polarity protection of supply voltage
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off5 µA
RDS(on)140 mΩ
Peak short-circuit current<12 A
Switch-on in the event of overload shutdown or short-circuit shutdownApprox. 10 ms (depends on the module temperature)
Braking voltage when switching off inductive loadsTyp. 50 VDC
Insulation voltage between channel and bus500 Veff
Additional functionsOutputs can be connected in parallel to increase the output current.
Electrical properties
Electrical isolationChannel isolated from bus and I/O power supply
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Starting temperatureYes, -40°C
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationUp to 100%, condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20cBM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.