IAC

B&R X20CP1382

Intel x86 400 MHz compatible with integrated I/O processor Ethernet, POWERLINK with poll-response chaining and onboard USB 1 slot for modular interface expansion 30 digital inputs/outputs and 2 analog inputs integrated in the device 2 GB onboard flash drive 256 MB DDR3 SDRAM Fanless No battery Backed-up real-time clock The X20 Compact controller series is characterized by 3 integrated I/O modules. The device is equipped with 30 different digital inputs/outputs and 2 analog inputs. 1 analog input can be used for Pt1000 resistance temperature measurement. The X20CP1382 is equipped with an Intel x86 400 MHz compatible processor, 256 MB RAM and 2 GB built-in flash drive. The FRAM for storing remanent variables has 32 kB available. A fanless and battery-free design ensures maintenance-free operation. The controller is equipped with Ethernet, 2x USB and an RS232 interface. In addition, POWERLINK and CAN bus are available as integrated interfaces. For additional fieldbus connections, each controller can be expanded with an interface module from the X20 standard portfolio.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
Interfaces1x RS232, 1x Ethernet, 1x POWERLINK, 2x USB, 1x X2X Link, 1x CAN bus
System moduleController
General information
Diagnostics / OutputsDigital outputs: Yes, using LED status indicator and software (output error status)
Diagnostics / CPU functionYes, using LED status indicator
Diagnostics / CAN bus data transferYes, using LED status indicator
Diagnostics / RS232 data transferYes, using LED status indicator
Diagnostics / InputsAnalog inputs: Yes, using LED status indicator and software
Diagnostics / EthernetYes, using LED status indicator
Diagnostics / I/O power supplyYes, using LED status indicator
Diagnostics / POWERLINKYes, using LED status indicator
Diagnostics / Supply voltage monitoringYes, using LED status indicator
Diagnostics / TemperatureYes, using software register
Diagnostics / Terminating resistorYes, using LED status indicator
Support / Controller redundancyNo
Support / ACOPOS supportYes
Support / reACTION-capable I/O channelsNo
Support / Visual Components supportYes
Power consumption / Internal I/O2.3 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)Non-compliant
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
B&R ID code0xDABB
CoolingFanless
Status indicatorsCPU function, Ethernet, POWERLINK, RS232, CAN bus, CAN bus terminating resistor, PLC power supply, I/O power supply, I/O function per channel
Power consumption without interface module and USB5.5 W
Power consumption for X2X Link power supply0.8 W
Additional power dissipation caused by actuators (resistive) [W]-
Type of signal linesShielded lines must be used for all high-speed digital inputs/outputs, line length: Max. 20 m
CPU and X2X Link power supply
Input voltage24 VDC -15% / +20%
Input currentMax. 1 A
FuseIntegrated, cannot be replaced
Reverse polarity protectionYes
X2X Link power supply output
Nominal output power2 W
Parallel connectionYes
Redundant operationYes
Input I/O power supply
Input voltage24 VDC -15% / +20%
FuseRequired line fuse: Max. 10 A, slow-blow
Output I/O power supply
Nominal output voltage24 VDC
Permissible contact load10 A
Controller
Processor / L1 cache / Data code16 kB
Processor / L1 cache / Program code16 kB
Processor / TypeVx86EX
Processor / Clock frequency400 MHz
Processor / L2 cache128 kB
Standard memory / RAM256 MB DDR3 SDRAM
Application memory / Writable data amount / Guaranteed40 TB
Application memory / Writable data amount / Results for 5 years21.9 GB/day
Application memory / Type2 GB eMMC flash memory
Application memory / Data retention10 years
Application memory / Guaranteed erase/write cycles20,000
Application memory / Error-correcting code (ECC)Yes
Real-time clockRetention for at least 300 hours, typ. 1000 hours at 25°C, 1 s resolution, -18 to 28 ppm accuracy at 25°C
Floating point unit (FPU)Yes
Integrated I/O processorProcesses I/O data points in the background
Modular interface slots1
Remanent variables32 kB FRAM, retention >10 years
Shortest task class cycle time1 ms
Typical instruction cycle time0.0199 µs
Interfaces
Interface IF1 / SignalRS232
Interface IF1 / VariantConnection via 16-pin terminal block X20TB1F
Interface IF1 / Max. distance900 m
Interface IF1 / Transfer rateMax. 115.2 kbit/s
Interface IF2 / Transfer / Physical layer10BASE-T/100BASE-TX
Interface IF2 / Transfer / Half-duplexYes
Interface IF2 / Transfer / Full-duplexYes
Interface IF2 / Transfer / AutonegotiationYes
Interface IF2 / Transfer / Auto-MDI/MDIXYes
Interface IF2 / SignalEthernet
Interface IF2 / Variant1x RJ45 shielded
Interface IF2 / Line lengthMax. 100 m between 2 stations (segment length)
Interface IF2 / Transfer rate10/100 Mbit/s
Interface IF3 / Transfer / Physical layer100BASE-TX
Interface IF3 / Transfer / Half-duplexYes
Interface IF3 / Transfer / Full-duplexPOWERLINK mode: No / Ethernet mode: Yes
Interface IF3 / Transfer / AutonegotiationYes
Interface IF3 / Transfer / Auto-MDI/MDIXYes
Interface IF3 / FieldbusPOWERLINK managing or controlled node
Interface IF3 / TypeType 4
Interface IF3 / Variant1x RJ45 shielded
Interface IF3 / Line lengthMax. 100 m between 2 stations (segment length)
Interface IF3 / Transfer rate100 Mbit/s
Interface IF4 / TypeUSB 1.1/2.0
Interface IF4 / VariantType A
Interface IF4 / Max. output current0.5 A
Interface IF5 / TypeUSB 1.1/2.0
Interface IF5 / VariantType A
Interface IF5 / Max. output current0.1 A
Interface IF6 / FieldbusX2X Link master
Interface IF7 / SignalCAN bus
Interface IF7 / VariantConnection via 16-pin terminal block X20TB1F
Interface IF7 / Max. distance1000 m
Interface IF7 / Transfer rateMax. 1 Mbit/s
Interface IF7 / Terminating resistorIntegrated in module
Interface IF7 / ControllerSJA 1000
Digital inputs
Input filter / HardwareStandard inputs and mixed channels: ≤200 μs High-speed inputs: ≤2 μs, when used as standard inputs: ≤200 μs
Input filter / SoftwareDefault 1 ms, configurable between 0 and 25 ms in 0.1 ms increments
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Quantity14 standard inputs, 4 high-speed inputs and 4 mixed channels, configuration as input or output using software
Nominal voltage24 VDC
Input voltage24 VDC -15% / +20%
Input current at 24 VDCX1 - Standard inputs: Typ. 3.5 mA X2 - Standard inputs: Typ. 2.68 mA X2 - High-speed inputs: Typ. 3.5 mA X3 - Mixed channels: Typ. 2.68 mA
Input circuitSink
Connection type1-wire connections
Input resistanceX1 - Standard inputs: 6.8 kΩ X2 - Standard inputs: 8.9 kΩ X2 - High-speed inputs: 6.8 kΩ X3 - Mixed channels: 8.9 kΩ
Additional functionsX2 - High-speed digital inputs: 2x 250 kHz event counting, 2x AB counter, ABR incremental encoder, direction/frequency, period measurement, gate measurement, differential time measurement, edge counters, edge times
AB incremental encoder
Quantity2
Encoder inputs24 V, asymmetrical
Counter size32-bit
Input frequencyMax. 100 kHz
Evaluation4x
Encoder power supplyModule-internal, max. 300 mA
Overload characteristics of encoder power supplyShort-circuit proof, overload-proof
ABR incremental encoder
Quantity1
Encoder inputs24 V, asymmetrical
Counter size32-bit
Input frequencyMax. 100 kHz
Evaluation4x
Encoder power supplyModule-internal, max. 300 mA
Overload characteristics of encoder power supplyShort-circuit proof, overload-proof
Event counters
Quantity2
Signal formSquare wave pulse
Evaluation1x
Input frequencyMax. 250 kHz
Counter frequency250 kHz
Counter size32-bit
Edge detection / Time measurement
Possible measurementsPeriod measurement, gate measurement, differential time measurement, edge counter, edge times
Measurements per moduleEach function up to 2x
Signal formSquare wave pulse
Counter size32-bit
Input frequencyMax. 10 kHz
Timestamp1 µs resolution
Analog inputs
Digital converter resolution / Voltage±12-bit
Digital converter resolution / Current12-bit
Output format / Data typeINT
Output format / VoltageINT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
Output format / CurrentINT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 μA
Input impedance in signal range / Voltage20 MΩ
Input impedance in signal range / Current-
Load / Voltage-
Load / Current<300 Ω
Permissible input signal / VoltageMax. ±30 V
Permissible input signal / CurrentMax. ±50 mA
Max. error / Voltage / Gain0.18% (Rev. <C0: 0.37%)
Max. error / Voltage / Offset0.04% (Rev. <C0: 0.25%)
Max. error / Current / Gain0 to 20 mA = 0.15% (Rev. <C0: 0.52%) / 4 to 20 mA = 0.25%
Max. error / Current / Offset0 to 20 mA = 0.1% (Rev. <C0: 0.4%) / 4 to 20 mA = 0.15%
Max. gain drift / Voltage0.017 %/°C
Max. gain drift / Current0 to 20 mA = 0.015 %/°C / 4 to 20 mA = 0.023 %/°C
Max. offset drift / Voltage0.008 %/°C
Max. offset drift / Current0 to 20 mA = 0.008 %/°C / 4 to 20 mA = 0.012 %/°C
Common-mode rejection / DC70 dB
Common-mode rejection / 50 Hz70 dB
Nonlinearity / Voltage<0.025%
Nonlinearity / Current<0.05%
Input±10 V or 0 to 20 mA / 4 to 20 mA, via different terminal connections
Input typeDifferential input
Conversion time1 channel enabled: 100 µs 2 channels enabled: 200 µs
Input protectionProtection against wiring with supply voltage
Output of digital value during overloadConfigurable
Conversion procedureSAR
Input filterThird-order low-pass filter / Cutoff frequency 1 kHz
Common-mode range±12 V
Crosstalk between channels<-70 dB
Resistance measurement temperature inputs
Sensor / Pt1000-200 to 850°C
Max. error at 25°C / Gain0.3% (Rev. <C0: 1.93%)
Max. error at 25°C / Offset0.15% (Rev. <C0: 0.32%)
Common-mode rejection / 50 Hz>60 dB
Temperature sensor normalization / Pt1000-200 to 850°C
Quantity1
InputResistance measurement with constant current supply for 2-wire connections
Digital converter resolution13-bit
Conversion timeOnly temperature input enabled: 200 µs Temperature and analog input enabled: 400 µs
Conversion procedureSAR
Output formatINT or UINT for resistance measurement
Resistance measurement range0.1 to 4000 Ω
Temperature sensor resolution1 LSB = 0x0005 = 0.16°C
Resistance measurement resolution1 LSB = 0x0005 = 0.49 Ω
Input filterFirst-order low-pass filter / cutoff frequency 7 Hz
Sensor standardEN 60751
Common-mode range1 V
Linearization methodInternal
Measuring current1 mA
Permissible input signalShort-term max. ±30 V
Max. gain drift0.023 %/°C
Max. offset drift0.012%/°C
Nonlinearity<0.05%
Standardized range of values for resistance measurement0.1 to 4000.0 Ω
Crosstalk between channels<-70 dB
Digital outputs
Pulse width modulation / Period duration5 to 65535 µs corresponds to 200 kHz to 15 Hz
Pulse width modulation / Pulse duration0 to 100%, minimum 2.5 µs
Pulse width modulation / Resolution for pulse duration0.1% of the configured frequency
Switching delay / 0 → 1Standard outputs and mixed channels: <300 µs High-speed outputs: <3 µs
Switching delay / 1 → 0Standard outputs and mixed channels: <300 µs High-speed outputs: <3 µs
Switching frequency / Resistive loadStandard outputs and mixed channels: Max. 500 Hz High-speed outputs: 50 kHz, max. 200 kHz (see section "Switching frequency derating for high-speed digital outputs")
Switching frequency / Inductive loadSee section "Switching inductive loads".
Quantity4 standard outputs, 4 high-speed outputs and 4 mixed channels, configuration as input or output using software
VariantStandard outputs and mixed channels: Current-sourcing FET High-speed outputs: Push-Pull
Nominal voltage24 VDC
Switching voltage24 VDC -15% / +20%
Nominal output currentStandard outputs and mixed channels: 0.5 A High-speed outputs: 0.2 A
Total nominal currentStandard outputs and mixed channels: 4 A High-speed outputs: 0.8 A
Connection type1-wire connections
Output circuitStandard outputs and mixed channels: Source High-speed outputs: Sink or source
Output protectionThermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current") Internal freewheeling diode for switching inductive loads (see section "Switching inductive loads")
Diagnostic statusStandard outputs and mixed channels: Output monitoring with 10 ms delay High-speed outputs: Output monitoring with 10 µs delay
Leakage current when the output is switched offStandard outputs and mixed channels: 5 µA High-speed outputs: 25 µA
RDS(on)140 mΩ
Residual voltageStandard outputs and mixed channels: <0.1 V at nominal current 0.5 A High-speed outputs: <0.9 V at nominal current 0.1 A
Peak short-circuit currentStandard outputs and mixed channels: <3 A High-speed outputs: <20 A
Switch-on in the event of overload shutdown or short-circuit shutdownStandard outputs and mixed channels: Approx. 10 ms (depends on module temperature) High-speed outputs: No switch-on
Braking voltage when switching off inductive loadsStandard outputs and mixed channels: Typ. 45 VDC
Electrical properties
Electrical isolationEthernet (IF2), POWERLINK (IF3) and X2X (IF6) isolated from each other, from other interfaces and from PLC Channel isolated from bus Channel not isolated from channel or PLC
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Switching frequency derating for high-speed digital outputs".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
Dimensions / Width164 mm
Dimensions / Height99 mm
Dimensions / Depth75 mm
NoteX20 end cover plate (right) included in delivery 3 X20 terminal blocks (16-pin) included in delivery Interface module slot cover included in delivery
Weight310 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.