B&R X20cSO4120

4 safe digital outputs with 2 A Source circuit Output type A Current monitoring Open circuit detection Integrated output protection This module is equipped with 4 safe digital outputs. The nominal output current is 2 A. The module can be used for controlling actuators in safety-related applications up to PL e or SIL 3. The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The "high-side low-side" variant (output type A) is limited to actuators without reference potential (e.g. relays, valves). Type A outputs have safety-related advantages since the actuator can be cut off in its connection cable in all error scenarios. Safe digital output channels provide protection against automatic restart when network errors occur and also using a current measurement for open circuit detection. This module is designed for X20 12-pin terminal blocks.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module4 safe type A digital outputs, with current monitoring, 24 VDC, 2 A, OSSD <500 µs
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator and software
Blackout mode / ScopeModule
Blackout mode / FunctionModule functionality
Blackout mode / Standalone modeNo
Power consumption / Bus0.25 W
Power consumption / Internal I/O1.3 W
Electrical isolation / Channel - BusYes
Electrical isolation / Channel - ChannelNo
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / Functional safetycULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013
Certifications / Functional safety #2IEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3
Certifications / Functional safety #3EN 50156-1:2004
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC21B Temperature: 5 - 45°C Vibration: 0.7 g EMC: Bridge and open deck
B&R ID code0xDD5C
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]2.16
Safety characteristics
NoteSee section "Safety characteristics".
I/O power supply
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protective functionReverse polarity protection
Safe digital outputs
Quantity4
VariantFET, 1x positive switching, 1x negative switching, type A, output level readable, open-circuit detection
Nominal voltage24 VDC
Nominal output current2 A
Total nominal current5 A
Output protectionSee section "Inrush current behavior for output channels".
Braking voltage when switching off inductive loadsMax. 90 VDC
Open-circuit detectionVia internal current measurement, output current <10 mA: Signal "CurrentOK" = FALSE, output current 10 to 50 mA: Signal "CurrentOK" = Undefined, output current >50 mA: Signal "CurrentOK" = TRUE
Error detection time1 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section "Inrush current behavior for output channels".
Leakage current when the output is switched off<10 µA
RDS(on)240 mΩ
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section "Inrush current behavior for output channels".
Test pulse lengthMax. 500 µs
Time between two test pulsesMin. 49.5 ms
Max. capacitive load100 nF
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Starting temperatureYes, -40°C
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / OperationUp to 100%, condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Pitch25⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.