IAC

B&R X20DC1178

1 SSI absolute encoder 5 V Monitoring the data signal 2 additional inputs 5 VDC, 24 VDC and GND for encoder supply NetTime timestamp: Counter change Can be used with a SafeLOGIC controller This module is equipped with 1 input for SSI absolute encoders with 5 V encoder signal. The data signal is monitored (Data, Data\).

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module1 SSI absolute encoder 5 V
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Power consumption / Bus0.01 W
Power consumption / Internal I/O1.1 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0xA708
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Type of signal linesShielded lines must be used for all signal lines.
Digital inputs
Input filter / Hardware≤2 µs
Input filter / Software-
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Quantity2
Nominal voltage24 VDC
Input characteristics per EN 61131-2Type 1
Input voltage24 VDC -15% / +20%
Input current at 24 VDCApprox. 3.3 mA
Input circuitSink
Connection type3-wire connections
Input resistance7.03 kΩ
Insulation voltage between channel and bus500 Veff
SSI absolute encoder
Encoder power supply / 5 VDC±5%, module-internal, max. 300 mA
Encoder power supply / 24 VDCModule-internal, max. 300 mA
Switching threshold / Low>1 V
Encoder inputs5 V, symmetrical
Counter sizeUp to 32-bit depending on encoder
Max. transfer rate1 Mbit/s
CodingGray/Binary
Minimum diff. slew rate1 V/μs
Insulation voltage between encoder and bus500 Veff
Overload characteristics of encoder power supplyShort-circuit proof, overload-proof
Transfer rate125 kbit/s / 250 kbit/s / 500 kbit/s / 1 Mbit/s
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.