IAC

B&R X20DC1398

1 SSI absolute encoder 24 V 1 additional input 24 VDC and GND for encoder supply This module is equipped with one input for SSI absolute encoders with 24 V encoder signal.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module1 SSI absolute encoder 24 V
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Power consumption / Bus0.01 W
Power consumption / Internal I/O1.3 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
Input voltage24 VDC -15% / +20%
B&R ID code0x1BAE
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Type of signal linesShielded lines must be used for all signal lines.
Digital inputs
Input filter / Hardware≤2 µs
Input filter / Software-
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Quantity1
Nominal voltage24 VDC
Input characteristics per EN 61131-2Type 1
Input current at 24 VDCApprox. 3.3 mA
Input circuitSink
Connection type3-wire connections
Input resistance7.19 kΩ
Insulation voltage between channel and bus500 Veff
SSI absolute encoder
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Encoder inputs24 V, asymmetrical
Counter size32-bit
Max. transfer rate125 kbit/s
Encoder power supplyModule-internal, max. 600 mA
CodingGray/Binary
CLK: Output currentMax. 100 mA
DATA: Input resistance18.4 kΩ
Insulation voltage between encoder and bus500 Veff
Overload characteristics of encoder power supplyShort-circuit proof, overload-proof
Electrical properties
Electrical isolationBus isolated from encoder and channel Channel not isolated from encoder
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.