IAC

B&R X20DID371

8 digital inputs Sink connection 2-wire connections 24 VDC for sensor supply Software input filter can be configured for entire module The module is equipped with 8 inputs for 1-wire or 2-wire connections. The module is designed for sink input wiring.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module8 digital inputs 24 VDC for 1- or 2-wire connections
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Power consumption / Bus0.13 W
Power consumption / Internal I/O1.2 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0xC0E7
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Digital inputs
Input filter / Hardware≤100 μs
Input filter / SoftwareDefault 1 ms, configurable between 0 and 25 ms in 0.2 ms increments
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Nominal voltage24 VDC
Input characteristics per EN 61131-2Type 1
Input voltage24 VDC -15% / +20%
Input current at 24 VDCTyp. 3.75 mA
Input circuitSink
Connection type1- or 2-wire connections
Input resistanceTyp. 6.4 kΩ
Sensor power supply0.5 A summation current
Insulation voltage between channel and bus500 Veff
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB1F separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.