IAC

B&R X20DO4623

4 digital outputs Outputs with integrated snubber circuit Outputs with 100 to 240 VAC L switching 50 Hz or 60 Hz 2-wire connections Integrated full-wave control 240 V coding The module is a digital output module that is equipped with 4 SSR outputs with zero cross-over switches and uses 2-line connections. The module is also equipped with integrated full-wave control. The supply (L and N) is fed directly to the module.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module4 digital SSR outputs 100 to 240 VAC for 2-wire connections
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator
Power consumption / Bus0.52 W
Power consumption / Internal I/O-
Power consumption / External I/O0.38 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
B&R ID code0x267C
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]+3.2
Digital outputs
Switching delay / At 50 Hz / 0 → 1≤11 ms
Switching delay / At 50 Hz / 1 → 0≤11 ms
Switching delay / At 60 Hz / 0 → 1≤9.3 ms
Switching delay / At 60 Hz / 1 → 0≤9.3 ms
Output voltage / Minimum75 VAC
Protective circuit / ExternalGenerally varistor or fuse
Protective circuit / InternalSnubber circuit (RC element)
VariantSSR
CircuitL-switching
Nominal voltage100 to 240 VAC
Max. voltage264 VAC
Rated frequency47 to 63 Hz
Nominal output current0.5 A
Total nominal current1 A
Surge current7 A (20 ms), 2 A (1 s)
Connection type2-wire connections
Zero-crossing switchesYes
Leakage currentMax. 1.5 mA at 240 V
Residual voltage (on-state voltage)1.6 V
Insulation voltage between channel and busTested at 2500 VAC
Voltage monitoring L - NNo
Overvoltage protection between L and NYes
Electrical properties
Electrical isolationChannel isolated from bus and I/O power supply
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mNot permitted
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB32 separately. Order 1x bus module X20BM12 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.