IAC

B&R X20DO4F49

4 digital outputs Relay module for 250 VDC / 240 VAC 2 normally open contacts and 2 changeover contacts Single-channel isolated outputs This module is equipped with 4 relay outputs (2 normally open and 2 changeover contacts each) for 250 VDC / 240 VAC. The outputs are single-channel isolated.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module4 digital outputs 250 VDC / 240 VAC, outputs single-channel isolated
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator
Power consumption / Bus1.1 W
Power consumption / Internal I/O-
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / Functional safetyIEC 61508 in preparation EN 62061 in preparation EN ISO 13849-1 in preparation IEC 61511 in preparation
Certifications / ULcULus E115267 Industrial control equipment
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
B&R ID code0xF76A
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]+0.32
Digital outputs
Switching delay / 0 → 1Normally open contact ≤15 ms / Changeover contact ≤19 ms
Switching delay / 1 → 0Normally open contact ≤11 ms / Changeover contact ≤15 ms
Insulation voltages / Channel - BusTested at 3500 VAC
Insulation voltages / Channel - ChannelTested at 1700 VAC
Insulation voltages / Channel - GroundTested at 3500 VAC
Service life / Electrical10⁵ at 2 A (normally open contact and changeover contact)
Service life / Mechanical30 x10⁶ cycles (normally open contact and changeover contact)
Switching capacity / Minimum0.12 W DC / 2.4 W AC
Switching capacity / MaximumDC: See section "DC switching capacity". AC: 480 W
Protective circuit / External / ACRC combination or VDR
Protective circuit / External / DCInverse diode, RC combination or VDR
Protective circuit / InternalNone
VariantRelays: 2 normally open contacts and 2 changeover contacts Channels are single-channel isolated.
Nominal voltage250 VDC / 240 VAC
Max. voltage250 VAC
Switching voltageMax. 250 VDC / 250 VAC
Rated frequencyDC / 45 to 63 Hz
Nominal output currentDC: See section "DC switching capacity". AC: 2 A at 240 VAC
Total nominal currentDC: See section "DC switching capacity". AC: 8 A at 240 VAC
Actuator power supplyExternal
Inrush currentMax. 8 A (per channel)
Contact resistanceMax. 100 mΩ
Electrical properties
Electrical isolationChannel isolated from channel, bus and I/O power supply
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB32 separately. Order 1x bus module X20BM32 separately.
Pitch25⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.