IAC

B&R X20DO6321

6 digital outputs Sink connection 2-wire connections 24 VDC for signal supply Integrated output protection 1-wire connection type with 6-pin terminal block The module is equipped with 6 outputs for 1- or 2-wire connections. The outputs are designed for a sink circuit. For continuous 1-wire wiring, the 6x X20 terminal block can be used. 2-wire wiring can be implemented with the 12x terminal block.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module6 digital outputs 24 VDC for 1- or 2-wire connections
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator and software (output error status)
Power consumption / Bus0.2 W
Power consumption / Internal I/O0.59 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
B&R ID code0x1B99
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]+0.18
Digital outputs
Switching delay / 0 → 1<300 µs
Switching delay / 1 → 0<300 µs
Switching frequency / Resistive loadMax. 500 Hz
Switching frequency / Inductive loadSee section "Switching inductive loads".
VariantFET current-sinking
Nominal voltage24 VDC
Switching voltage24 VDC -15% / +20%
Nominal output current0.5 A
Total nominal current3 A
Connection type1- or 2-wire connections
Output circuitSink
Output protectionThermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current") Internal freewheeling diode for switching inductive loads (see section "Switching inductive loads")
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off75 µA
RDS(on)120 mΩ
Peak short-circuit current<7 A
Switch-on in the event of overload shutdown or short-circuit shutdownApprox. 10 ms (depends on the module temperature)
Braking voltage when switching off inductive loadsTyp. 50 VDC
Insulation voltage between channel and bus500 Veff
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel and I/O power supply
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB06 or X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.