IAC

B&R X20DS1828

HIPERFACE encoder interface Encoder input monitoring 11 VDC and GND for encoder supply NetTime timestamp: Position time The module is equipped with 1 HIPERFACE encoder interface. This module can be used to evaluate encoders installed in motors from other manufacturers as well as encoders for external axes (encoders that sample any machine movement). The input signals are monitored. This makes it possible to detect open or shorted lines as well as encoder supply failures.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module1x HIPERFACE interface
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / Counting directionYes, using LED status indicator
Power consumption / Bus0.01 W
Power consumption / Internal I/O1.3 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
B&R ID code0xAEC7
Status indicatorsCounting direction, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Type of signal linesShielded lines must be used for all signal lines.
Encoder inputs
Sine/Cosine inputs / Signal transmissionDifferential signals, symmetrical
Sine/Cosine inputs / Signal frequencyDC up to 200 kHz
Sine/Cosine inputs / Differential voltage1 VSS
Sine/Cosine inputs / Common-mode voltageMax. ±10 V
Sine/Cosine inputs / Terminating resistor120 Ω
Angular position resolution13-bit, with a signal of 1 VSS
Encoder monitoringYes
Max. encoder cable length10 m
Encoder power supply
Protective measures / Overload-proofYes
Protective measures / Short-circuit proofYes
Output voltage11 V
Load capacity150 mA
Parameter channel (RS485)
Signal transmission5 VDC differential signal, EiA RS485 standard
Transmission statusSee the HIPERFACE specification.
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.