4 IO-Link interfaces per module Each interface can be configured as a standard input or output Seamless integration in POWERLINK Supports all transfer rates IO-Link is a standardized communication system for connecting intelligent sensors and actuators in an automation system. The standardization includes electrical connection data as well as a digital communication protocol, which is used by the sensors and actuators in the automation system for data exchange. An IO-Link system consists of an IO-Link master and one or more IO-Link devices, i.e. sensors and actuators. The IO-Link master makes the interface available for higher level control and controls communication with the connected IO-Link devices. An IO-Link device is an intelligent sensor or actuator. With regard to IO-Link, "intelligent" means that a device possesses a series number or parameter data (sensitivity, switching delays or characteristic curves), which can be written to or read via the IO-Link protocol. Process optimization The use of intelligent sensors and actuators contributes to process optimization. Process optimization means that downtimes should be kept as short as possible. These consist mainly of standstills due to errors and setup times. Integrated communication down to the IO-Link devices offers many advantages in error diagnostics. Errors are detected much faster than before. If a sensor or actuator must be replaced, lengthy configuration work is no longer necessary after the change thanks to a potentiometer, or a configuration tool and laptop. After changing the sensor/actuator, the parameters are automatically transferred to the sensor. This parameter download is not only beneficial when errors occur. It can also be used for changing parameters when a load change is performed. This shortens setup times, making product changes and small batches more economical. Integrating IO-Link into the X20 System IO-Link is integrated in the X20 system using this digital module. All 4 channels are IO-Link interfaces, but can also be used as standard inputs or outputs. The specified 3-wire connections can be ideally implemented thanks to the X20 connector system with 12 terminal points per module. All specified transfer rates are also supported. POWERLINK integration IO-Link doesn't stop at the I/O module. It must be integrated in the higher-level bus system to fully utilize the benefits. When using POWERLINK, access is made possible via device description files in XML format.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O moduleIO-Link master with 4 IO-Link interfaces
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / IO-Link operating stateYes, using LED status indicator and software
Diagnostics / C/Q statusYes, using LED status indicator and software
Cable specification / Cable type3-pin standard sensor cable
Cable specification / Cable lengthMax. 20 m
Cable specification / Line capacitanceMax. 3 nF
Cable specification / Loop resistanceMax. 6 Ω
Power consumption / Bus0.01 W
Power consumption / Internal I/O1.6 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
B&R ID code0xA38E
Status indicatorsIO-Link, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Sensor/Actuator power supply
VoltageI/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.3 AMax. 1 VDC
Power consumptionMax. 9 W per interface
Short-circuit proofYes
IO-Link in master mode
Transfer rates / COM14.8 kbaud
Transfer rates / COM238.4 kbaud
Transfer rates / COM3230.4 kbaud
Limit values for COM3 / Max. connection capacity47 nF (cable and device)
Limit values for COM3 / Max. load100 Ω / 0.3 A
Data format1 start bit, 8 data bits, 1 parity bit (even), 1 stop bit
Bus level24 VDC (active), 0 VDC (resting voltage)
IO-Link device power supply24 VDC / Max. 0.3 A per interface (fused)
IO-Link in master mode or in SIO mode "digital output"
Switching delay / 0 → 1<10 µs
Switching delay / 1 → 0<10 µs
VariantBipolar, positive and negative switching
DiagnosticsOutput monitoring with 100 ns delay and internal protection of the semiconductor with 100 µs delay
Peak short-circuit current<1.5 A
Residual voltage<1.5 VDC at nominal current 0.2 A
Switching voltageI/O power supply minus voltage drop for short-circuit protection and semiconductor switch
Voltage drop on semiconductor switchMax. 1.5 VDC at 0.2 A
Switching frequencyTyp. 25 kHz 300 kHz in IO-Link master mode
Switch-on in the event of overload shutdown or short-circuit shutdownApprox. 10 ms (depends on the module temperature)
Braking voltage when switching off inductive loadsTyp. 52 VDC
Insulation voltage between IO-Link and bus500 Veff
IO-Link in SIO mode "Digital output"
Nominal voltage24 VDC
Nominal output current0.2 A
Total nominal current0.4 A
Output circuitSink or source
Output protectionThermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads
Actuator power supply24 VDC / Max. 0.3 A per interface (fused)
IO-Link in SIO mode "digital input"
Input filter / Hardware100 ns
Input filter / Software-
Switching threshold / Low<8 VDC
Switching threshold / High>13 VDC
Nominal voltage24 VDC
Input circuitSink
Sensor power supply24 VDC / Max. 0.3 A per interface (fused)
Input voltage24 VDC -15% / +20%
Input current at 24 VDCTyp. 5 mA
Input resistanceTyp. 4.8 kΩ
Insulation voltage between IO-Link and bus500 Veff
Electrical properties
Electrical isolationBus isolated from IO-Link IO-Link not isolated from IO-Link
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation0 to 55°C
Temperature / Operation / Vertical mounting orientation0 to 45°C
Temperature / Derating-
Temperature / Storage-25 to 70°C
Temperature / Transport-25 to 70°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.