IAC

B&R X20HB8884

Connecting POWERLINK devices to the POWERLINK cable redundancy system Integrated compact link selector function POWERLINK is a standard protocol for Fast Ethernet with hard real-time properties. The Ethernet POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed. www.ethernet-powerlink.org Systems with redundant cabling can be implemented easily using POWERLINK. Unlike ring redundancy, cable redundancy does not require cable looping, which can sometimes be problematic. This allows the creation of all types of tree structures. When using a device with the link selector function, data is always transferred via the highest quality network lines. The link selector function is integrated in the module compact link selector. This makes it easy to connect any POWERLINK device to a redundant POWERLINK network.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
POWERLINK compact link selectorConnects POWERLINK devices to a redundant POWERLINK network
General information
Diagnostics / Module statusYes, using LED status indicator
Diagnostics / Bus functionYes, using LED status indicator
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
Status indicatorsModule status, bus function
Power consumption2 W
Interfaces
Transfer / Physical layer100BASE-TX
Transfer / Half-duplexYes
Transfer / Full-duplexNo
Transfer / AutonegotiationYes
Transfer / Auto-MDI/MDIXYes
TypePOWERLINK compact link selector
Variant2x shielded RJ45
Line lengthMax. 100 m between 2 stations (segment length)
Transfer rate100 Mbit/s
Hub propagation delay0.96 to 1 µs
Electrical properties
Electrical isolationPower supply isolated from POWERLINK (IF1 and IF2)
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
Pitch / X20BB8162.5⁺⁰.² mm
Pitch / X20BB8287.5⁺⁰.² mm
NoteOrder 1x terminal block X20TB12 separately. Order 1x power supply module X20PS8002 separately. Order 1x hub expansion module X20HB2880 or 2x hub expansion module X20HB2885. Order 1x bus base X20BB81 or X20BB82 separately.

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.