B&R X20IF1061
PROFIBUS DP V1 master The interface module can be used to expand the X20 CPU for specific applications. It is equipped with a PROFIBUS DP V1 master interface.
Lifecycle & replacement
Lifecycle status not indexed
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| Communication module | PROFIBUS DP V0/V1 master |
General information
| Diagnostics / Module status | Yes, using LED status indicator and software |
| Diagnostics / Bus status | Yes, using LED status indicator and software |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Certifications / HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Certifications / KC | Yes |
| B&R ID code | 0x1F22 |
| Status indicators | Module status, bus status |
| Power consumption | 1.4 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
Interfaces
| Interface IF1 / Cyclic data / Input data | 3.5 kB |
| Interface IF1 / Cyclic data / Output data | 3.5 kB |
| Interface IF1 / Fieldbus | PROFIBUS DP V0/V1 master |
| Interface IF1 / Variant | 9-pin female DSUB connector |
| Interface IF1 / Max. distance | 1200 m |
| Interface IF1 / Transfer rate | Max. 12 Mbit/s |
| Interface IF1 / Terminating resistor | External using T-connector (0G1000.00-090) |
| Interface IF1 / Controller | EC1 |
| Interface IF1 / Memory | 8 MB SDRAM |
Electrical properties
| Electrical isolation | PLC isolated from PROFIBUS (IF1) |
Operating conditions
| Mounting orientation / Horizontal | Yes |
| Mounting orientation / Vertical | Yes |
| Installation elevation above sea level / 0 to 2000 m | No limitation |
| Installation elevation above sea level / >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature / Operation / Horizontal mounting orientation | -25 to 60°C |
| Temperature / Operation / Vertical mounting orientation | -25 to 50°C |
| Temperature / Derating | - |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
| Relative humidity / Operation | 5 to 95%, non-condensing |
| Relative humidity / Storage | 5 to 95%, non-condensing |
| Relative humidity / Transport | 5 to 95%, non-condensing |
Mechanical properties
| Slot | In the X20 PLC |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
ECAD / EPLAN
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.