IAC

B&R X20IF2792

X2X Link connection CAN bus connection Integrated terminating resistor The interface module is used for application-specific expansion of the X20 controllers. It is equipped with an X2X Link interface and a CAN bus interface.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
Communication module1x X2X Link master, 1x CAN bus
General information
Diagnostics / Module statusYes, using LED status indicator
Diagnostics / Data transferYes, using LED status indicator
Diagnostics / Terminating resistorYes, using LED status indicator
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
B&R ID code0x1F26
Status indicatorsModule status, data transfer, terminating resistor
Power consumption1.25 W (rev. <E0: 1.51 W)
Additional power dissipation caused by actuators (resistive) [W]-
Interfaces
Interface IF1 / FieldbusX2X Link master
Interface IF1 / Variant4-pin male multipoint connector
Interface IF1 / Number of stationsMax. 253
Interface IF1 / Internal bus power supplyNo
Interface IF1 / Network topologyLine
Interface IF1 / Distance between 2 stationsMax. 100 m
Interface IF1 / Bus terminating resistorInternal
Interface IF2 / SignalCAN bus
Interface IF2 / Variant5-pin male multipoint connector
Interface IF2 / Max. distance1000 m
Interface IF2 / Transfer rateMax. 1 Mbit/s
Interface IF2 / Terminating resistorIntegrated in module
Interface IF2 / ControllerSJA 1000
Electrical properties
Electrical isolationPLC isolated from X2X Link (IF1) and CAN (IF2) and interfaces isolated from each other
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block TB704 and 1x terminal block TB2105 separately.
SlotIn the X20 PLC

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.