IAC

B&R X20PS4951

Open circuit and short circuit detection Simple implementation of potentiometer inputs 4x supply In order to connect potentiometers, modules must first be supplied with the appropriate voltage. The potentiometer supply module can be used to supply four potentiometers with ±10 V. The data is evaluated using standard analog input modules.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
System modulePower supply of 4 potentiometers with ±10 V
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / Open circuitYes, using LED status indicator and software
Diagnostics / OverloadYes, using LED status indicator and software
Power consumption / Bus0.01 W
Power consumption / Internal I/O1.8 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0x1F43
Status indicatorsPotentiometer power supply monitoring per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]-
Potentiometer power supply
Basic accuracy / +10 V±0.12% at 25°C
Basic accuracy / -10 V±0.21% at 25°C
Basic accuracy / 20 V±0.165% at 25°C
Max. drift / +10 V±0.00012 %/°C
Max. drift / -10 V±0.00032 %/°C
Max. drift / 20 V±0.00022 %/°C
Number of power supplies4
Voltage±10 V
Potentiometer resistance1 kΩ to 10 kΩ
LoadMax. 20 mA per power supply channel
Short-circuit proofYes
Insulation voltage between channel and bus500 Veff
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.