IAC

B&R X20PS9502

Supply for Compact or Fieldbus CPU, X2X Link network and internal I/O power supply Cost-effective power supply module for small X20 systems No electrical isolation of supply and CPU / X2X Link power supply Expansion or redundancy of CPU / X2X Link power supply not possible by operating multiple power supply modules simultaneously RS232 configurable as an online interface CAN bus The power supply module is used together with an X20 Compact or Fieldbus CPU. It is equipped with a supply for the Compact or Fieldbus CPU, X2X Link network and internal I/O power supply. This module is intended as a cost-effective power supply module for small X20 systems. The use of potential groups is possible. Expansion or redundancy of the X2X Link network with power supply module X20PS3300 or X20PS3310 is not possible. Expanding the X20 system with a bus transmitter is also not permitted.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
Power supply module24 VDC power supply module for Compact or Fieldbus CPU, X2X Link power supply and I/O
Interfaces1x RS232, 1x CAN bus
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / CAN bus data transferYes, using LED status indicator
Diagnostics / RS232 data transferYes, using LED status indicator
Diagnostics / OverloadYes, using LED status indicator and software
Power consumption / Internal I/O0.6 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0xA38A
Status indicatorsOperating state, module status, RS232, CAN bus
Power consumption for X2X Link power supply1.64 W
Additional power dissipation caused by actuators (resistive) [W]-
CPU / X2X Link power supply input
Input voltage24 VDC -15% / +20%
Input currentMax. 0.7 A
FuseIntegrated, cannot be replaced
Reverse polarity protectionYes
CPU / X2X Link power supply output
Nominal output power / Horizontal mounting orientation7 W at 45°C and 5 W at 55°C
Nominal output power / Vertical mounting orientation7 W at 40°C and 5 W at 50°C
Parallel connectionNo
Redundant operationNo
Overload characteristicsShort-circuit proof, temporary overload
Input I/O power supply
Input voltage24 VDC -15% / +20%
FuseRequired line fuse: Max. 10 A, slow-blow
Reverse polarity protectionNo
Output I/O power supply
Nominal output voltage24 VDC
Behavior on short circuitRequired line fuse
Permissible contact load10 A
Interfaces
Interface IF1 / SignalRS232
Interface IF1 / VariantConnection via 12-pin terminal block X20TB12
Interface IF1 / Transfer rateMax. 115.2 kbit/s
Interface IF3 / SignalCAN bus
Interface IF3 / VariantConnection via 12-pin terminal block X20TB12
Interface IF3 / Transfer rateMax. 1 Mbit/s
Electrical properties
Electrical isolationCPU/X2X Link supply not isolated from CPU/X2X Link power supply, and I/O supply not isolated from I/O power supply
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation-25 to 60°C
Temperature / Operation / Vertical mounting orientation-25 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x terminal block X20TB12 separately. Order 1x Compact CPU base X20BB22 or X20BB27 separately Order 1x Fieldbus CPU base X20BB32 or X20BB37 separately
Pitch12.5⁺⁰.² mm