IAC

B&R X20SI4100

4 safe digital inputs 4 pulse outputs Sink circuit Software input filter configurable for each channel This module is equipped with 4 safe digital inputs. It is designed for a nominal voltage of 24 VDC. The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3. The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line. This module is designed for X20 12-pin terminal blocks.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module4 safe type A digital inputs, 4 pulse outputs, 24 VDC
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / InputsYes, using LED status indicator and software
Blackout mode / ScopeModule
Blackout mode / FunctionModule functionality
Blackout mode / Standalone modeNo
Power consumption / Bus0.32 W
Power consumption / Internal I/O1.25 W
Electrical isolation / Channel - BusYes
Electrical isolation / Channel - ChannelNo
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / Functional safetycULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013
Certifications / Functional safety #2IEC 61508, up to SIL 3 IEC 62061, up to SIL 3 ISO 13849-1, up to Cat. 4 / PL e IEC 61511, up to SIL 3
Certifications / Functional safety #3EN 50156-1
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment cULus E537419 Engine generator controller
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / DNVTemperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
Certifications / CCSYes
Certifications / LRENV1
Certifications / KRYes
Certifications / ABSYes
Certifications / BVEC21B Temperature: 5 - 45°C Vibration: 0.7 g EMC: Bridge and open deck
Certifications / KCYes
B&R ID code0x1DBD
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]0.6
Safety characteristics
NoteSee section "Safety characteristics".
I/O power supply
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protective functionReverse polarity protection
Safe digital inputs
Input filter / Hardware≤150 μs
Input filter / SoftwareConfigurable between 0 and 500 ms
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Quantity4
VariantType A
Nominal voltage24 VDC
Input characteristics per EN 61131-2Type 1
Input circuitSink
Input voltage24 VDC -15% / +20%
Input current at 24 VDCMin. 2 mA to max. 4.59 mA. Hardware revision J0 and later: Min. 2 mA to max. 3.28 mA.
Input resistanceMin. 5.23 kΩ, hardware revision J0 and later: Min. 7.33 kΩ
Error detection time100 ms
Insulation voltage between channel and bus500 Veff
Line length between signal source (pulse output or external signal) and inputMax. 60 m with unshielded line Max. 400 m with shielded line
Pulse outputs
Quantity4
VariantPush-Pull
Nominal output current100 mA, hardware revision J0 and later: 50 mA
Output protectionThermal shutdown of all channels in the event of overload or short circuit, hardware revision J0 and later: Shutdown of individual channels in the event of overload or short circuit
Peak short-circuit current300 mA, hardware revision J0 and later: 25 A for 15 µs
Short-circuit current100 mAeff
Leakage current when the output is switched off0.1 mA
RDS(on)60 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Total nominal current400 mA, hardware revision J0 and later: 200 mA
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation0 to 60°C
Temperature / Operation / Vertical mounting orientation0 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Pitch25⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.