B&R X20SL8011
SafeLOGIC controllers handle all central tasks within a safety-related application. Three different functional areas exist here. The configuration management system monitors the entire safety-related configuration of the application. When replacements are needed, the parameter management system makes sure that newly installed modules are assigned correct parameters that apply to the application. Lastly, SafeLOGIC handles the actual safety-related execution of the application program.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| Interfaces | POWERLINK |
| System module | CPU |
General information
| System requirements / Automation Studio | 3.0.80 or later |
| System requirements / Automation Runtime | 3.00 or later |
| System requirements / SafeDESIGNER | 2.71 and later, up to 3.0 |
| System requirements / Safety Release | 1.3 and later, up to 1.6 |
| Diagnostics / CPU function | Yes, using LED status indicator |
| Diagnostics / POWERLINK | Yes, using LED status indicator |
| Diagnostics / SafeKEY | Yes, using LED status indicator |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / Functional safety | cULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013 |
| Certifications / Functional safety #2 | IEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3 |
| Certifications / Functional safety #3 | EN 50156-1:2004 |
| Certifications / ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Certifications / HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Certifications / DNV | Temperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck) |
| Certifications / CCS | Yes |
| Certifications / LR | ENV1 |
| Certifications / KR | Yes |
| Certifications / ABS | Yes |
| Certifications / BV | EC21B Temperature: 5 - 45°C Vibration: 0.7 g EMC: Bridge and open deck |
| Certifications / KC | Yes |
| Cooling | Fanless |
| Status indicators | CPU function, POWERLINK, SafeKEY |
| Power consumption | 5.1 W |
Safety characteristics
| EN ISO 13849-1:2015 / Category | Cat. 4 |
| EN ISO 13849-1:2015 / PL | PL e |
| EN ISO 13849-1:2015 / DC | >94% |
| EN ISO 13849-1:2015 / MTTFD per channel | 2500 years |
| EN ISO 13849-1:2015 / Mission time | Max. 20 years |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 / PFH / PFHd / Module | <1*10⁻¹⁰ |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 / PFH / PFHd / openSAFETY wired | Negligible |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 / PFH / PFHd / openSAFETY wireless | <1*10⁻¹⁴ * Number of openSAFETY packets per hour |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 / SIL CL | SIL 3 |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 / SFF | >90% |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 / PFD per channel | <2*10⁻⁵ |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 / Proof test interval (PT) | 20 years |
Functionality
| Number of supported safety nodes | Max. 100 |
| Communication with each other | Free communication with max. 10 other SafeLOGIC controllers possible |
| Support for machine options | Yes |
| SafeMOTION support | Yes |
| Shortest task class cycle time | 1 ms |
Fieldbus
| Type | POWERLINK |
| Variant | Internal 2-port hub, 2x shielded RJ45 port |
| Line length | Max. 100 m between 2 stations (segment length) |
| Transfer rate | 100 Mbit/s |
| Cycle time | Max. 20 ms |
Power supply
| Nominal voltage | 24 VDC -15% / +20% |
| Fuse | Integrated, cannot be replaced |
| Reverse polarity protection | Yes |
Operating conditions
| Mounting orientation / Horizontal | Yes |
| Mounting orientation / Vertical | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature / Operation / Horizontal mounting orientation | 0 to 55°C |
| Temperature / Operation / Vertical mounting orientation | 0 to 45°C |
| Temperature / Derating | - |
| Temperature / Storage | -25 to 70°C |
| Temperature / Transport | -25 to 70°C |
| Relative humidity / Operation | 5 to 95%, non-condensing |
| Relative humidity / Storage | 5 to 95%, non-condensing |
| Relative humidity / Transport | 5 to 95%, non-condensing |
Mechanical properties
| Dimensions / Width | 87.5⁺⁰.² mm |
| Dimensions / Height | 99 mm |
| Dimensions / Depth | 75 mm |
| Note | Order application memory (SafeKEY) separately. X20 end cover plate (right) is included in delivery. 12-pin X20 terminal block, safety-keyed, is included in delivery. SafeKEY cover is included in delivery. |
| Weight | 290 g |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
3D CAD models
ECAD / EPLAN
Certificates
- 2226379 CSA Certificate of Compliance X20 X67
- 64331_A1 BV Certificate of Compliance X20
- 64331_A1 BV Certificate of Compliance X20(de)
- ABS Certificate of Product Design Assessment - X20 IO Series
- CCS Type Approval Certificate - X20
- E115267 UL Certificate of Compliance X20
- EU Declaration of Conformity CE_Declaration_FS_X20
- FS EN 50156 Zertifikat SafeLOGIC, SafeIO
- FTZU 09 ATEX 0083X
- KR Type Approval Certificate MIL39390-AC003 (X20 System)
- Lloyds Register (X20 only)
- M6A 041745 0010 TÜV Süd FS Certificate SafeDESIGNER, SafeLOGIC, SafeIO
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.