IAC

B&R X20SLX842-1

X20 SafeLOGIC-X controller (Safety+) 8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B digital outputs, 24 VDC, 50 mA, OSSD <500 µs

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B2 digital outputs, 24 VDC, 50 mA, OSSD <500 µs, SafeLOGIC-X technology
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator and software
Diagnostics / InputsYes, using LED status indicator and software
Blackout mode / ScopeModule
Blackout mode / FunctionProgrammable
Blackout mode / Standalone modeYes
Power consumption / Bus0.4 W
Power consumption / Internal I/O2.5 W
Additional power dissipation caused by actuators (resistive) [W] / Safe digital HS-LS outputs0.84
Additional power dissipation caused by actuators (resistive) [W] / Safe digital HS-HS outputs0.175
Additional power dissipation caused by actuators (resistive) [W] / Pulse outputs0.8
Electrical isolation / Channel - BusYes
Electrical isolation / Channel - ChannelNo
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / Functional safetyIEC 61508, up to SIL 3 IEC 62061, up to SIL 3 ISO 13849-1, up to Cat. 4 / PL e IEC 61511, up to SIL 3
Certifications / Functional safety #2EN 50156-1
Certifications / ATEXIn preparation
Certifications / ULcULus E115267 Industrial control equipment cULus E537419 Engine generator controller
B&R ID code0x2F20
Status indicatorsI/O function per channel, operating state, module status
Safety characteristics
NoteSee section "Safety characteristics".
Safe digital inputs
Input filter / Hardware≤150 µs
Input filter / SoftwareConfigurable between 0 and 500 ms
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Quantity8
VariantType A
Nominal voltage24 VDC
Input characteristics per EN 61131-2Type 1
Input circuitSink
Input voltage24 VDC -15% / +20%
Input current at 24 VDCMin. 2 mA to max. 3.28 mA
Input resistanceMin. 7.33 kΩ
Error detection time100 ms
Insulation voltage between channel and bus500 Veff
Line length between signal source (pulse output or external signal) and inputMax. 60 m with unshielded line Max. 400 m with shielded line
Safe digital HS-LS outputs
Quantity4
VariantFET, 1x positive switching, 1x negative switching, type A, output level readable
Nominal voltage24 VDC
Nominal output current3 A
Total nominal current10 A
Output protectionSee section "Inrush current behavior for output channels".
Braking voltage when switching off inductive loadsMax. 90 VDC
Error detection1 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section "Inrush current behavior for output channels".
Leakage current when the output is switched off<1 mA
RDS(on)30 mΩ
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section "Inrush current behavior for output channels".
Test pulse lengthMax. 500 µs
Max. capacitive load100 nF
Safe digital HS-HS outputs
Quantity2
VariantFET, 2x positive switching, type B2, output level readable
Nominal voltage24 VDC
Nominal output current50 mA
Total nominal current100 mA
Output protectionSee section "Inrush current behavior for output channels".
Braking voltage when switching off inductive loadsMax. 45 VDC
Error detection time1 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section "Inrush current behavior for output channels".
Leakage current when the output is switched off<1 mA
RDS(on)35 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section "Inrush current behavior for output channels".
Test pulse lengthMax. 500 µs
Max. capacitive load100 nF
Current on loss of ground
IOUT<100 µA
IGND<50 mA
Pulse outputs
Quantity4
VariantPush-Pull
Nominal output current50 mA
Output protectionShutdown of individual channels in the event of overload or short circuit
Peak short-circuit current0.5 A for 120 µs
Short-circuit current15 mAeff
Leakage current when the output is switched off0.1 mA
RDS(on)80 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Total nominal current200 mA
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation0 to 60°C
Temperature / Operation / Vertical mounting orientation0 to 50°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 2x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Pitch25⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.