IAC

B&R X20SP1130

24 VDC power supply module for internal I/O power supply Safe cutoff of potential groups with standard outputs Safely switched potential can also be tapped externally 1 safe digital output with 10 A Source circuit Output type B Integrated output protection This module is equipped with 1 safe digital output. The nominal output current is 10 A. The power supply module is used for the internal I/O power supply. A safe digital output channel is integrated in the module for cutting off the I/O power supply of connected X20 modules in safety-related applications up to PL e or SIL 3. The output is designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The "High-side-High-side" variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. In addition, the instructions for switching off X20 potential groups must be observed. The safe digital output channel provides protection against automatic restart when network errors occur. This module is designed for X20 12-pin terminal blocks.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module1 safe type B1 digital output, 24 VDC, 10 A, without OSSD, note list of permitted modules in the potential group
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / OutputsYes, using LED status indicator and software
Blackout mode / ScopeModule
Blackout mode / FunctionModule functionality
Blackout mode / Standalone modeNo
Power consumption / Bus0.2 W
Power consumption / Internal I/O1.5 W
Electrical isolation / Channel - BusYes
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / Functional safetycULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013
Certifications / Functional safety #2IEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3
Certifications / Functional safety #3EN 50156-1:2004
Certifications / ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
Certifications / ULcULus E115267 Industrial control equipment cULus E537419 Engine generator controller
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
B&R ID code0x1DBF
Status indicatorsI/O function per channel, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]3
Safety characteristics
NoteSee section "Safety characteristics".
Input I/O power supply
Input voltage24 VDC -15% / +20%
FuseRequired line fuse: Max. 10 A, slow-blow
Reverse polarity protectionNo
Safe digital outputs
Quantity1
ExecutionFET, 2x positive switching, type B1, output level readable
Nominal voltage24 VDC
Nominal output current10 A
Output protectionSee section "Inrush current behavior for output channels".
Braking voltage when switching off inductive loads1 VDC
Diagnostic statusOutput monitoring, current measurement (shutdown in the event of overcurrent)
Error detection time2 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section "Inrush current behavior for output channels".
Leakage current when the output is switched off1 mA
RDS(on)30 mΩ
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequency5 times per minute with max. 2 Hz Hardware upgrade 2.2.0.0 and later: 120 times per minute with max. 2 Hz See section "Inrush current behavior for output channels" and table "Switching inductive loads".
Test pulse lengthWithout test pulse
Max. capacitive load1 mF
Minimum load15 mA
Current on loss of ground
IOUT<1 mA
IGND<50 mA
Operating conditions
Mounting orientation / HorizontalYes
Mounting orientation / VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Ambient conditions
Temperature / Operation / Horizontal mounting orientation0 to 60°C
Temperature / Operation / Vertical mounting orientation0 to 35°C
Temperature / DeratingSee section "Derating".
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%, non-condensing
Relative humidity / Storage5 to 95%, non-condensing
Relative humidity / Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Pitch25⁺⁰.² mm

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.