B&R X67AM1223
2 analog inputs, 2 analog outputs, ±10 V each Open circuit detection on the inputs Configurable digital input filters Very short cycle times Optimal shield grounding on all channels The module is equipped with 2 inputs and 2 outputs with 12-bit digital converter resolution. The range of the input/output signal is ±10 V.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| I/O module | 2 analog inputs, 2 analog outputs, each ±10 V |
General information
| Diagnostics / Inputs | Yes, using LED status indicator and software |
| Diagnostics / I/O power supply | Yes, using LED status indicator and software |
| Connection type / X2X Link | M12, B-coded |
| Connection type / Inputs/Outputs | 4x M12, A-coded |
| Connection type / I/O power supply | M8, 4-pin |
| Power consumption / Internal I/O | 3 W |
| Power consumption / X2X Link power supply | 0.75 W |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| Certifications / ATEX | Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X |
| Certifications / UL | cULus E115267 Industrial control equipment |
| Certifications / HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Certifications / KC | Yes |
| B&R ID code | 0x1465 |
| Status indicators | I/O function per channel, supply voltage, bus function |
I/O power supply
| Power consumption / Sensor/Actuator power supply | Max. 12 W |
| Nominal voltage | 24 VDC |
| Voltage range | 18 to 30 VDC |
| Integrated protective function | Reverse polarity protection |
Sensor/Actuator power supply
| Voltage | I/O power supply minus voltage drop for short-circuit protection |
| Voltage drop for short-circuit protection at 0.5 A | Max. 2 VDC |
| Summation current | Max. 0.5 A |
| Short-circuit proof | Yes |
Analog inputs
| Output format / Voltage | INT 0x8001 - 0x7FFF / 1 LSB = 0x0010 = 4.882 mV |
| Output of digital value during overload / Undershoot | 0x8001 |
| Output of digital value during overload / Overshoot | 0x7FFF |
| Max. error / Gain | 0.1% |
| Max. error / Offset | 0.05% |
| Common-mode rejection / DC | >50 dB |
| Common-mode rejection / 50 Hz | >50 dB |
| Input filter / Cutoff frequency | 300 Hz |
| Input filter / Slope | 40 dB |
| Input | ±10 V |
| Input type | Differential input |
| Digital converter resolution | 12-bit |
| Conversion time | 400 µs for both inputs |
| Output format | INT |
| Input impedance in signal range | 20 MΩ |
| Input protection | Protection against wiring with supply voltage |
| Permissible input signal | Max. ±30 V |
| Conversion procedure | Successive approximation |
| Max. gain drift | 0.011%/°C |
| Max. offset drift | 0.009%/°C |
| Common-mode range | ±11 V |
| Crosstalk between channels | <-70 dB |
| Nonlinearity | <0.1% |
| Insulation voltage between channel and bus | 500 Veff |
Analog outputs
| Short-circuit proof / Current limiting | ±40 mA |
| Short-circuit proof / To GND | Yes |
| Short-circuit proof / To sensor or I/O power supply | Yes |
| Max. error at 25°C and 10 kΩ load / Gain | 0.15% |
| Max. error at 25°C and 10 kΩ load / Offset | 0.05% |
| Output | ±10 V |
| Digital converter resolution | 12-bit |
| Conversion time | 400 µs for both outputs |
| Settling time on output change over entire range | Approx. 1 ms |
| Switch on/off behavior | Internal enable relay for startup and errors |
| Output protection | Protection against wiring with supply voltage, short-circuit proof |
| Output format | INT 0x8001 - 0x7FFF / 1 LSB = 0x0010 = 4.882 mV |
| Load per channel | Max. ±10 mA, load ≥ 1 kΩ |
| Output filter | First-order low-pass filter / cutoff frequency 2.5 kHz |
| Max. gain drift | 0.012%/°C |
| Max. offset drift | 0.015%/°C |
| Error caused by load change | Max. 0.01%, from 10 MΩ → 1 kΩ, resistive |
| Nonlinearity | <0.15% |
| Insulation voltage between channel and bus | 500 Veff |
| Output response when the power supply is switched on/off | An enable relay is switched on at a defined value ≠ 0, default setting = 10 kΩ to GND |
Electrical properties
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
Operating conditions
| Mounting orientation / Any | Yes |
| Installation elevation above sea level / 0 to 2000 m | No limitation |
| Installation elevation above sea level / >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP67 |
Ambient conditions
| Temperature / Operation | -25 to 60°C |
| Temperature / Derating | - |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
Mechanical properties
| Dimensions / Width | 53 mm |
| Dimensions / Height | 85 mm |
| Dimensions / Depth | 42 mm |
| Torque for connections / M8 | Max. 0.4 Nm |
| Torque for connections / M12 | Max. 0.6 Nm |
| Weight | 195 g |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
3D CAD models
ECAD / EPLAN
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.