IAC

B&R X67AM1323

2 analog inputs, 2 analog outputs, each 0 to 20 mA Configurable digital input filters Very short cycle times Optimal shield grounding on all channels The module is equipped with 2 inputs and 2 outputs with 12-bit digital converter resolution. The range of the input/output signal is 0 to 20 mA.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module2 analog inputs, 2 analog outputs, each 0 to 20 mA
General information
Diagnostics / InputsYes, using LED status indicator and software
Diagnostics / I/O power supplyYes, using LED status indicator and software
Connection type / X2X LinkM12, B-coded
Connection type / Inputs/Outputs4x M12, A-coded
Connection type / I/O power supplyM8, 4-pin
Power consumption / Internal I/O3 W
Power consumption / X2X Link power supply0.75 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
B&R ID code0x1466
Status indicatorsI/O function per channel, supply voltage, bus function
I/O power supply
Power consumption / Sensor/Actuator power supplyMax. 12 W
Nominal voltage24 VDC
Voltage range18 to 30 VDC
Integrated protective functionReverse polarity protection
Sensor/Actuator power supply
VoltageI/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 AMax. 2 VDC
Summation currentMax. 0.5 A
Short-circuit proofYes
Analog inputs
Output format / CurrentINT 0x0000 - 0x7FFF / 1 LSB = 0x0010 = 4.883 µA
Output of digital value during overload / Undershoot0x0000
Output of digital value during overload / Overshoot0x7FFF
Max. error / Gain0.1%
Max. error / Offset0.05%
Common-mode rejection / DC>50 dB
Common-mode rejection / 50 Hz>50 dB
Input filter / Cutoff frequency300 Hz
Input filter / Slope40 dB
Input0 to 20 mA
Input typeDifferential input
Digital converter resolution12-bit
Conversion time400 µs for both inputs
Output formatINT
Load<300 Ω
Input protectionProtection against wiring with supply voltage
Permissible input signalMax. ±30 V
Conversion procedureSuccessive approximation
Max. gain drift0.013 %/°C
Max. offset drift0.02 %/°C
Common-mode range±11 V
Crosstalk between channels<-70 dB
Nonlinearity<0.1%
Insulation voltage between channel and bus500 Veff
Analog outputs
Short-circuit proof / Current limiting±40 mA
Short-circuit proof / To GNDYes
Short-circuit proof / To sensor or I/O power supplyYes
Max. error at 25°C and 50 Ω load / Gain0.2%
Max. error at 25°C and 50 Ω load / Offset0.05%
Output0 to 20 mA
Digital converter resolution12-bit
Conversion time400 µs for both outputs
Settling time on output change over entire rangeApprox. 1 ms
Switch on/off behaviorInternal enable relay for startup and errors
Output protectionProtection against wiring with supply voltage, short-circuit proof
Output formatINT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Load per channelMax. load is 400 Ω
Output filterFirst-order low-pass filter / cutoff frequency 1.5 kHz
Max. gain drift0.015%/°C
Max. offset drift0.032%/°C
Error caused by load changeMax. 0.5%, from 1 Ω → 400 Ω, resistive
Nonlinearity<0.1%
Insulation voltage between channel and bus500 Veff
Output response when the power supply is switched on/offAn enable relay is switched on at a defined value ≠ 0, default setting = 10 kΩ to GND
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / AnyYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP67
Ambient conditions
Temperature / Operation-25 to 60°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Mechanical properties
Dimensions / Width53 mm
Dimensions / Height85 mm
Dimensions / Depth42 mm
Torque for connections / M8Max. 0.4 Nm
Torque for connections / M12Max. 0.6 Nm
Weight175 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.