IAC

B&R X67AT1311

4 inputs for resistance temperature measurement with 3 different resolutions Additional direct resistance measurement with 2 different resolutions Configuration can be set for each channel 2-wire and 4-wire measurement The module is a temperature module for Pt100 resistance temperature sensors. The sensors can be connected with 2-wire or 4-wire connections.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module4 inputs for Pt100 or resistance measurement
General information
Diagnostics / InputsYes, using LED status indicator and software
Diagnostics / I/O power supplyYes, using LED status indicator and software
Connection type / X2X LinkM12, B-coded
Connection type / Inputs4x M12, A-coded
Connection type / I/O power supplyM8, 4-pin
Power consumption / Internal I/O1.5 W
Power consumption / X2X Link power supply0.75 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
B&R ID code0xD21B
Status indicatorsI/O function per channel, supply voltage, bus function
I/O power supply
Nominal voltage24 VDC
Voltage range18 to 30 VDC
Integrated protective functionReverse polarity protection
Resistance measurement temperature inputs
Conversion time / Same sensor types75 ms per channel with 50 Hz filter
Sensor / Pt100-200 to 270°C (at 0.01 K resolution) -200 to 645°C (at 0.02 K resolution) -200 to 850°C (at 0.04 K resolution)
Max. error at 25°C / Gain0.008%
Max. error at 25°C / Offset0.012%
Temperature sensor resolution / Pt1001 LSB = 0.01 K (up to 270°C) 1 LSB = 0.02 K (up to 645°C) 1 LSB = 0.04 K (up to 850°C)
Resistance measurement resolution / Measurement range up to 420 Ω1 LSB = 10 mΩ
Resistance measurement resolution / Measurement range up to 210 Ω1 LSB = 5 mΩ
Input filter / Cutoff frequency115 Hz / First-order filter
Input filter / Slope-20 dB
Common-mode rejection / 50 Hz>70 dB
Common-mode rejection / DC>70 dB
Temperature measurement monitoring / Range undershoot0x8001
Temperature measurement monitoring / Range overshoot0x7FFF
Temperature measurement monitoring / Open circuit0x7FFF
Temperature measurement monitoring / General fault0x8000
Temperature measurement monitoring / Open inputs0x7FFF
Resistance measurement monitoring / Range undershoot0x0000
Resistance measurement monitoring / Range overshoot0xFFFF
Resistance measurement monitoring / Open circuit0xFFFF
Resistance measurement monitoring / General fault0xFFFF
Resistance measurement monitoring / Open inputs0xFFFF
InputResistance measurement with constant current supply for 2- or 4-wire connections
Digital converter resolution16-bit
Filter timeConfigurable between 2 and 20 ms
Conversion procedureSigma-delta
Output formatINT or UINT for resistance measurement
Pt100 temperature measurement rangeConfigurable per channel
Resistance measurement range0.010 to 420 Ω / 0.005 to 210 Ω
Sensor standardEN 60751
Common-mode range±1 VDC
Insulation voltage between channel and bus500 Veff
Linearization methodSoftware
Measuring current1.014 mA ±1.25%
Reference422 Ω ±0.05%
Permissible input signalShort-term max. ±30 V
Max. gain drift0.0008%/°C
Max. offset drift0.0006%/°C
Nonlinearity<0.002%
Crosstalk between channels-70 dB
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / AnyYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP67
Ambient conditions
Temperature / Operation-25 to 60°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Mechanical properties
Dimensions / Width53 mm
Dimensions / Height85 mm
Dimensions / Depth42 mm
Torque for connections / M8Max. 0.4 Nm
Torque for connections / M12Max. 0.6 Nm
Weight205 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.