B&R X67BC8513.L12-1
POWERLINK V1/V2 Integrated hub for economical wiring 12 digital channels, configurable as inputs or outputs 1 analog input, 0 to 20 mA, 12-bit M8 connection type I/O configuration and firmware update via the fieldbus Integrated connection to the local expansion via X2X Link for up to 250 additional modules Configurable I/O cycle (starting at 200 µs) The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler. Additional X2X Link I/O nodes (X67 modules or other modules based on X2X Link) can be connected using the integrated X2X Link connection. Mechanically, POWERLINK is connected via an IP67-rated standard D-coded M12 Ethernet connector. POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.
Lifecycle & replacement
No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.
IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.
Technical specifications
Short description
| Bus controller | POWERLINK (V1/V2) controlled node |
General information
| B&R ID code / Bus controller | 0x046C |
| B&R ID code / Internal I/O module | 0x04A8 |
| Diagnostics / Outputs | Yes, using LED status indicator and software |
| Diagnostics / I/O power supply | Yes, using LED status indicator and software |
| Support / Dynamic node allocation (DNA) | Yes |
| Connection type / Fieldbus | M12, D-coded |
| Connection type / X2X Link | M12, B-coded |
| Connection type / Inputs/Outputs | 8x M12, A-coded |
| Connection type / I/O power supply | M8, 4-pin |
| Power consumption / Fieldbus | 2.5 W |
| Power consumption / Internal I/O | 0.6 W |
| Power consumption / X2X Link power supply | 17.25 W at maximum power output for connected I/O modules |
| Certifications / CE | Yes |
| Certifications / UKCA | Yes |
| Certifications / CRA (Cyber Resilience Act) | In preparation |
| Inputs/Outputs | 6 digital inputs, 6 digital outputs (not configurable), inputs with additional function, 1 analog channel |
| Insulation voltage between channel and bus | 500 Veff |
| Nominal voltage | 24 VDC |
| Sensor/Actuator power supply | 0.5 A summation current |
| Status indicators | I/O function per channel, supply voltage, bus function |
| Power output | 15 W X2X Link power supply for I/O modules |
Interfaces
| Transfer / Physical layer | 100BASE-TX |
| Transfer / Half-duplex | Yes |
| Transfer / Full-duplex | No |
| Transfer / Autonegotiation | Yes |
| Transfer / Auto-MDI/MDIX | Yes |
| Min. cycle time / Fieldbus | 200 μs |
| Min. cycle time / X2X Link | 250 μs |
| Fieldbus | POWERLINK (V1/V2) controlled node |
| Type | Type 2 |
| Variant | 2x M12 interface (hub), 2x female connector on module |
| Line length | Max. 100 m between 2 stations (segment length) |
| Transfer rate | 100 Mbit/s |
| Hub propagation delay | 0.96 to 1 µs |
| Synchronization between bus systems possible | Yes |
I/O power supply
| Power consumption / Sensor/Actuator power supply | Max. 12 W |
| Nominal voltage | 24 VDC |
| Voltage range | 18 to 30 VDC |
| Integrated protective function | Reverse polarity protection |
Sensor/Actuator power supply
| Voltage | I/O power supply minus voltage drop for short-circuit protection |
| Voltage drop for short-circuit protection at 0.5 A | Max. 2 VDC |
| Summation current | Max. 0.5 A |
| Short-circuit proof | Yes |
Digital inputs
| Switching threshold / Low | <5 VDC |
| Switching threshold / High | >15 VDC |
| Input characteristics per EN 61131-2 | Type 1 |
| Input voltage | 18 to 30 VDC |
| Input current at 24 VDC | Typ. 4 mA |
| Input circuit | Sink |
| Input resistance | Typ. 6 kΩ |
Edge detection / Time measurement
| Counter frequency / Internal | 10 kHz |
| Signal form | Square wave pulse |
| Counter size | 16-bit |
| Pulse length | >200 µs with 200 µs pause between pulses |
| Measurement type | Propagation delay measurement between output and corresponding feedback input |
Analog inputs
| Output format / Current | 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 μA |
| Output of digital value during overload / Undershoot | 0x0000 |
| Output of digital value during overload / Overshoot | 0x7FFF |
| Max. error / Gain | 0.1% |
| Max. error / Offset | 0.05% |
| Common-mode rejection / DC | >50 dB |
| Common-mode rejection / 50 Hz | >50 dB |
| Input filter / Cutoff frequency | 1 kHz |
| Input filter / Slope | 40 dB |
| Input | 0 to 20 mA |
| Input type | Differential input |
| Digital converter resolution | 12-bit |
| Conversion time | 200 µs |
| Output format | INT |
| Load | <300 Ω |
| Input protection | Protection against wiring with supply voltage |
| Permissible input signal | Max. ±30 mA |
| Conversion procedure | Successive approximation |
| Max. gain drift | 0.013 %/°C |
| Max. offset drift | 0.02 %/°C |
| Common-mode range | ±2 V |
| Crosstalk between channels | >70 dB |
| Nonlinearity | <0.1% |
| Insulation voltage between input and bus | 500 Veff |
| Voltage drop at 20 mA | Typ. 4.5 V |
Digital outputs
| Switching delay / 0 → 1 | <400 µs |
| Switching delay / 1 → 0 | <400 µs |
| Switching frequency / Resistive load | Max. 100 Hz |
| Switching frequency / Inductive load | See section "Switching inductive loads". |
| Variant | Current-sourcing FET |
| Switching voltage | I/O power supply minus residual voltage |
| Nominal output current | 0.5 A |
| Total nominal current | 8 A |
| Output circuit | Source |
| Output protection | Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply |
| Diagnostic status | Output monitoring with 10 ms delay |
| Leakage current when the output is switched off | 5 µA |
| Switching on after overload shutdown | Approx. 10 ms (depends on the module temperature) |
| RDS(on) | 150 mΩ |
| Residual voltage | <0.3 V at 0.5 A nominal current |
| Peak short-circuit current | <12 A |
| Braking voltage when switching off inductive loads | 50 VDC |
Electrical properties
| Electrical isolation | Bus isolated from POWERLINK and channel Channel not isolated from channel |
Operating conditions
| Mounting orientation / Any | Yes |
| Installation elevation above sea level / 0 to 2000 m | No limitation |
| Installation elevation above sea level / >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP67 |
Ambient conditions
| Temperature / Operation | -25 to 60°C |
| Temperature / Derating | - |
| Temperature / Storage | -40 to 85°C |
| Temperature / Transport | -40 to 85°C |
Mechanical properties
| Dimensions / Width | 53 mm |
| Dimensions / Height | 155 mm |
| Dimensions / Depth | 42 mm |
| Torque for connections / M8 | Max. 0.4 Nm |
| Torque for connections / M12 | Max. 0.6 Nm |
| Weight | 360 g |
Documentation & CAD
Files hosted by B&R Industrial Automation; links open the official download page.
Datasheets
Manuals
ECAD / EPLAN
Get a quote for a replacement
Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.
Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.