Fieldbus: EtherCAT 16 digital channels, configurable as inputs or outputs Auto-configuration of I/O modules I/O configuration and firmware update via the fieldbus (FoE) Integrated connection to local expansion via X2X Link for 250 additional modules Full support of the modular slice concept via CoE (CANopen over EtherCAT) Configurable I/O cycle (0.2 to 4 ms) Synchronization between the fieldbus and X2X Link EtherCAT is an Ethernet-based fieldbus developed by Beckhoff. This protocol is suitable for both hard and soft real-time requirements in automation technology. In addition to a ring structure, which becomes logically necessary because of the summation frame telegram used, the EtherCAT technology also physically supports topologies such as line, tree, star (limited) and combinations of these topologies. B&R's X20BC80G3 (expandable bus controller module) and X20HB88G0 (standalone junction base module) are available for implementing these topologies. EtherCAT slave devices take the data designated for them from a telegram as it is passing through the device. Input data is also added to the telegram as it is passing through. The bus controller allows X2X Link I/O modules to be coupled to EtherCAT and operated on any EtherCAT master system. A transition between IP20 and IP67 protection outside of the control cabinet is possible by arranging X20, X67 or XV modules one after the other as needed at distances up to 100 m. Master systems without FoE (File access over EtherCAT) support require an appropriate configuration tool to transfer the configuration (optional). With multifunction modules, the bus controller supports only the default function model in the event of automatic configuration by the bus controller (see the respective module description). All other function models are supported when configured accordingly in Automation Studio V4.3 or later. Automation Studio kann kostenlos von der B&R Webseite www.br-automation.com heruntergeladen werden. Die Evaluierungslizenz darf unentgeltlich zur Erstellung vollständiger Konfigurationen der Feldbus Bus Controller benützt werden.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
Bus controllerEtherCAT
General information
B&R ID code / Bus controller0xACF8
B&R ID code / Internal I/O module0xB402
Diagnostics / OutputsYes, using LED status indicator and software
Diagnostics / I/O power supplyYes, using LED status indicator and software
Connection type / FieldbusM12, D-coded
Connection type / X2X LinkM12, B-coded
Connection type / Inputs/Outputs8x M12, A-coded
Connection type / I/O power supplyM8, 4-pin
Power consumption / Fieldbus2.5 W
Power consumption / Internal I/O0.5 W
Power consumption / X2X Link power supply15% of the power output for X2X Link
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
Inputs/Outputs16 digital channels, configurable as inputs or outputs using Automation Studio or data point, inputs with additional functions
Insulation voltage between channel and bus500 Veff
Nominal voltage24 VDC
Sensor/Actuator power supply0.5 A summation current
Status indicatorsI/O function per channel, supply voltage, bus function
Power output15 W X2X Link power supply for I/O modules
Additional power dissipation caused by actuators (resistive) [W]0.6
Interfaces
Transfer / Physical layer100BASE-TX
Transfer / Half-duplexYes
Transfer / Full-duplexYes
Transfer / AutonegotiationYes
Transfer / Auto-MDI/MDIXYes
Min. cycle time / Fieldbus200 μs
Min. cycle time / X2X Link200 μs
FieldbusEtherCAT slave
VariantM12 interface (female) 2x on the module
Line lengthMax. 100 m between 2 stations (segment length)
Transfer rate100 Mbit/s
Hub propagation delay750 ns
Synchronization between bus systems possibleYes
I/O power supply
Power consumption / Sensor/Actuator power supplyMax. 12 W
Nominal voltage24 VDC
Voltage range18 to 30 VDC
Integrated protective functionReverse polarity protection
Sensor/Actuator power supply
VoltageI/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 AMax. 2 VDC
Summation currentMax. 0.5 A
Short-circuit proofYes
Digital inputs
Input filter / Hardware≤10 μs (channels 1 to 4) / ≤70 µs (channels 5 to 16)
Input filter / SoftwareDefault 0 ms, configurable between 0 and 25 ms in 0.2 ms intervals
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Input characteristics per EN 61131-2Type 1
Input voltage18 to 30 VDC
Input current at 24 VDCTyp. 4 mA
Input circuitSink
Input resistanceTyp. 6 kΩ
Additional functions50 kHz event counting, gate measurement
Event counters
Quantity2
Signal formSquare wave pulse
EvaluationEach negative edge, cyclic counter
Input frequencyMax. 50 kHz
Counter 1Input 1
Counter 2Input 3
Counter frequencyMax. 50 kHz
Counter size16-bit
Gate time measurement
Counter frequency / Internal48 MHz, 3 MHz, 187.5 kHz
Quantity1
Signal formSquare wave pulse
EvaluationPositive edge - Negative edge
Counter size16-bit
Length of pause between pulses≥100 µs
Pulse length≥20 µs
Supported inputsInput 2 or input 4
Digital outputs
Switching delay / 0 → 1<400 µs
Switching delay / 1 → 0<400 µs
Switching frequency / Resistive loadMax. 100 Hz
Switching frequency / Inductive loadSee section "Switching inductive loads".
VariantCurrent-sourcing FET
Switching voltageI/O power supply minus residual voltage
Nominal output current0.5 A
Total nominal current8 A
Output circuitSource
Output protectionThermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off5 µA
Switching on after overload shutdownApprox. 10 ms (depends on the module temperature)
RDS(on)150 mΩ
Residual voltage<0.15 V at 0.5 A nominal current
Peak short-circuit current<12 A
Braking voltage when switching off inductive loads50 VDC
Electrical properties
Electrical isolationBus isolated from EtherCAT and channel Channel not isolated from channel
Operating conditions
Mounting orientation / AnyYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP67
Ambient conditions
Temperature / Operation-25 to 60°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Mechanical properties
Dimensions / Width53 mm
Dimensions / Height155 mm
Dimensions / Depth42 mm
Torque for connections / M8Max. 0.4 Nm
Torque for connections / M12Max. 0.6 Nm
Weight370 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.