IAC

B&R X67DM9331.L12

8 digital channels, configurable as inputs or outputs Outputs can handle up to 2 A Node number switches for setting the X2X Link address Replacement of passive distributors All outputs with single-channel diagnostics Extensive additional status information This module is equipped with 8 digital channels that can be configured either as inputs or outputs. The inputs are designed for a sink circuit, and the outputs are designed for a source circuit. The outputs can be loaded with up to 2 A. The summation current is 8 A. The node number switch for setting the X2X Link address is a unique feature. When modular machine configurations change, it is required, for example, to define certain module groups at a fixed address that is independent of the preceding modules in the line. All subsequent standard modules refer to this offset and use it automatically for addressing purposes.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O module8 digital channels, configurable as inputs or outputs using software
General information
Sensor/Actuator power supply / Sensor/Actuator current0.1 A
Sensor/Actuator power supply / Summation current0.5 A
Diagnostics / OutputsYes, using LED status indicator and software
Diagnostics / I/O power supplyYes, using LED status indicator and software
Diagnostics / Sensor/Actuator power supplyYes, using LED status indicator and software
Connection type / X2X LinkM12, B-coded
Connection type / Inputs/Outputs8x M12, A-coded
Connection type / I/O power supplyM8, 4-pin
Power consumption / Internal I/O1.7 W
Power consumption / X2X Link power supply0.75 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ATEXZone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X
Certifications / ULcULus E115267 Industrial control equipment
Certifications / HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Certifications / KCYes
Insulation voltage between channel and bus500 Veff
Nominal voltage24 VDC
B&R ID code0x1B15
Status indicatorsI/O function per channel, sensor/actuator power supply per channel, supply voltage, bus function
I/O power supply
Power consumption / Sensor/Actuator power supplyMax. 12 W
Nominal voltage24 VDC
Voltage range18 to 30 VDC
Integrated protective functionReverse polarity protection
Sensor/Actuator power supply
VoltageI/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 AMax. 2 VDC
Summation currentMax. 0.5 A
Short-circuit proofYes
Digital inputs
Input filter / Hardware≤70 μs
Input filter / SoftwareDefault 0 ms, configurable between 0 and 25 ms in 0.2 ms intervals
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Input characteristics per EN 61131-2Type 1
Input voltage18 to 30 VDC
Input current at 24 VDCTyp. 4.4 mA
Input circuitSink
Input resistanceTyp. 5 kΩ
Digital outputs
Switching delay / 0 → 1<250 µs
Switching delay / 1 → 0<270 µs
Switching frequency / Resistive loadMax. 100 Hz
VariantCurrent-sourcing FET
Switching voltageI/O power supply minus residual voltage
Nominal output current2 A
Total nominal current8 A
Output circuitSource
Output protectionThermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off5 µA
Switching on after overload shutdownApprox. 10 ms (depends on the module temperature)
Residual voltage<0.5 V at 2 A nominal current
Peak short-circuit current<21 A
Braking voltage when switching off inductive loads50 VDC
Electrical properties
Electrical isolationChannel isolated from bus Channel not isolated from channel
Operating conditions
Mounting orientation / AnyYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP67
Ambient conditions
Temperature / Operation-25 to 60°C
Temperature / Derating-
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Mechanical properties
Dimensions / Width53 mm
Dimensions / Height155 mm
Dimensions / Depth42 mm
Torque for connections / M8Max. 0.4 Nm
Torque for connections / M12Max. 0.6 Nm
Weight325 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.