IAC

B&R X67DS838B.L12

2 IO-Link channels (port class B) 6 IO-Link channels (port class A) Port class A: Additional digital input per IO-Link connection Each IO-Link channel configurable as a digital input or output (SIO mode) 24 VDC and GND for sensor/actuator power supply Port class B: Additional 24 VDC and GND for sensor/actuator power supply NetTime timestamps: IO-Link data The module is an IO-Link master that allows intelligent sensors and actuators to be connected per the IO-Link standard. The module can operate up to 8 IO-Link devices. All IO-Link channels can also be operated in SIO mode and thus used as digital inputs or outputs. The module is also equipped with 6 additional digital inputs that can be used independently of the configuration of the IO-Link channels. Connectors 7 and 8 are designed as class B IO-Link ports and have an additional galvanically isolated supply voltage.

Lifecycle & replacement

Lifecycle status not indexed

No manufacturer-published lifecycle data for B&R part numbers is indexed here yet. Ask IAC to check availability and an upgrade path.

IAC stocks legacy spares and exchange units and quotes upgrade paths. Send us the nameplate details and we will confirm a compatible replacement.

Technical specifications

Short description
I/O moduleIO-Link master with 8 IO-Link interfaces
General information
Diagnostics / Module run/errorYes, using LED status indicator and software
Diagnostics / IO-Link operating stateYes, using LED status indicator and software
Diagnostics / C/Q statusYes, using LED status indicator and software
Diagnostics / I/Q statusYes, using LED status indicator and software
Connection type / X2X LinkM12, B-coded
Connection type / InputsM12, A-coded
Connection type / I/O power supplyM8, 4-pin
Cable specification / Cable type4-pin sensor cable, unshielded
Cable specification / Cable lengthMax. 20 m
Cable specification / Line capacitanceMax. 3 nF
Cable specification / Loop resistanceMax. 6 Ω
Power consumption / Internal I/O0.8 W via connection C 0.5 W via connection D
Power consumption / X2X Link power supply0.8 W
Certifications / CEYes
Certifications / UKCAYes
Certifications / CRA (Cyber Resilience Act)In preparation
Certifications / ULcTÜV SÜDus No. U10 041745 0020 Per UL 61010-2-201
B&R ID code0x2DB9
Status indicatorsIO-Link operating state, bus function, module status
Additional power dissipation caused by actuators (resistive) [W]-
I/O power supply
Nominal voltage24 VDC
Voltage range24 VDC ±25%
Integrated protective functionReverse polarity protection
Sensor/Actuator power supply
Overload protection / Switch-off delayConfigurable using software
Overload protection / Switch-off durationConfigurable using software
VoltageI/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 AMax. 0.3 V
Power consumptionMax. 12 W per IO-Link interface
Short-circuit proofYes
Class B sensor/actuator power supply
Voltage24 VDC ±25%
Voltage drop for short-circuit protection at 1.9 AMax. 0.3 V
Power consumptionMax. 72 W per IO-Link class B interface
Short-circuit proofYes
Overload protectionThermal shutdown in the event of overcurrent or short circuit
IO-Link in master mode
Transfer rates / COM14.8 kbaud
Transfer rates / COM238.4 kbaud
Transfer rates / COM3230.4 kbaud
Limit values for COM3 / Max. connection capacity22 nF (cable + IO-Link device)
Limit values for COM3 / Max. load96 Ω / 250 mA
Data format1 start bit, 8 data bits, 1 parity bit (even), 1 stop bit
Bus level24 VDC (active), 0 VDC (resting voltage)
IO-Link in master mode or in SIO mode "digital output"
Switching delay / 0 → 1<10 µs
Switching delay / 1 → 0<10 µs
Overload protection of C/Q output / Overcurrent thresholdConfigurable using software
Overload protection of C/Q output / Switch-off durationConfigurable using software
ExecutionBipolar, positive and negative switching
Peak short-circuit current<1.3 A
Residual voltage<0.7 VDC at nominal current 0.25 A
Switching voltageI/O power supply minus voltage drop for short-circuit protection and semiconductor switch
Voltage drop on semiconductor switchMax. 0.5 VDC at 0.25 A
IO-Link in SIO mode "Digital output"
Nominal voltage24 VDC
Nominal output current0.25 A
Total nominal current with actuator power supplyMax. 4 A
Output circuitSink or source
Switching frequency (resistive load)Max. 500 Hz
Output protectionThermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads
IO-Link in SIO mode "digital input"
Input filter / Hardware300 ns
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Nominal voltage24 VDC
Input circuitSink
Input voltage24 VDC -15% / +20%
Input current at 24 VDCTyp. 2.4 mA
Input resistanceTyp. 10 kΩ
IO-Link I/Q interface (digital input)
Input filter / Hardware≤60 µs
Input filter / SoftwareDefault 1 ms, configurable between 0 and 25.5 ms
Switching threshold / Low<5 VDC
Switching threshold / High>15 VDC
Nominal voltage24 VDC
Input voltage24 VDC -15% / +20%
Input current at 24 VDCTyp. 3.6 mA
Input circuitSink
Input resistanceTyp. 6.3 kΩ
Electrical properties
Electrical isolationBus isolated from IO-Link
Operating conditions
Mounting orientation / AnyYes
Installation elevation above sea level / 0 to 2000 mNo limitation
Installation elevation above sea level / >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP67
Ambient conditions
Temperature / Operation-25 to 60°C
Temperature / Storage-40 to 85°C
Temperature / Transport-40 to 85°C
Relative humidity / Operation5 to 95%
Relative humidity / Storage5 to 95%
Relative humidity / Transport5 to 95%
Mechanical properties
Dimensions / Width53 mm
Dimensions / Height155 mm
Dimensions / Depth42 mm
Torque for connections / M8Max. 0.4 Nm
Torque for connections / M12Max. 0.6 Nm
Weight450 g

Documentation & CAD

Files hosted by B&R Industrial Automation; links open the official download page.

Get a quote for a replacement

Industrial Automation Co. stocks, sources, and repairs B&R parts — new, refurbished, or exchange units with warranty.

Specifications from the official B&R product catalog. Always confirm against the datasheet for your exact revision.